Enter the character string of the absolute address without empty spaces. The first
bit of a word has an address of 0.
8.4
Creating Tasks
Set the time response and the priority of individual tasks in the task configuration.
Watchdog
In an application program without task configuration, there is no watchdog that
monitors the cycle time of the application program (PLC_PRG).
Create a task as follows:
1.
Open the task configuration by double-clicking on the “Task configuration”
module in the “Resources” tab.
Figure 71: Task Configuration
2.
To create a task right-click on “Task configuration” and in the contextual
menu select “Attach task”.