3.2.2
Power Jumper Contacts/Field Supply
Pos: 31.1 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/Anschl üsse/Leistungskontakte 2 LK (Feder) - Ei nleitung @ 15\mod_1371724414861_21.docx @ 123722 @ @ 1
The power supply module 750-626 has 2 self-cleaning power jumper contacts that
transmit power for the field side. The contacts on the right side of the power
supply module are designed as spring contacts.
Pos: 31.2 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/Anschl üsse/Leistungskontakte 2 LK (Feder) - Abbil dung - Standar d @ 15\mod_1371548903658_21.docx @ 123408 @ @ 1
Figure 3: Power Jumper Contacts
Pos: 31.3 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/Anschl üsse/Leistungskontakte 2 LK (Feder) - Legende @ 15\mod_1371724465179_21.docx @ 123726 @ @ 1
Table 5: Legend for Figure “Power Jumper Contacts”
Contact
Type
Function
1
Spring contact
Potential feed-in (Uv) for field supply
2
Spring contact
Potential feed-in (0 V) for field supply
Pos: 31.4 /Serie 750 (WAGO-I/O-SYST EM)/Wichtige Erläuterungen/Sicherheits- und sonstig e Hinweise/Achtung/Achtung: M axi mal er Strom Leistungskontakte 10 A @ 3\mod_1226499143500_21.docx @ 25029 @ @ 1
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
Pos: 31.5 /Serie 750 (WAGO-I/O-SYST EM)/Wichtige Erläuterungen/Sicherheits- und sonstig e Hinweise/Hinweis/Hi nweis: Potenti alei nspeisekl emme für Erde ei nsetzen! ( kei ne LK für Erde) @ 3\mod_1226499037468_21.docx @ 25023 @ @ 1
Use supply modules for ground (earth)!
The I/O module has no power jumper contacts for receiving and transmitting the
earth potential. Use a supply module when an earth potential is needed for the
subsequent I/O modules.