WAGO-I/O-SYSTEM 750 XTR
Process Image 35
750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR
Manual
Version 1.3.0
Table 25: Control Byte C1
Control Byte C1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg_Com
0
0
0
0
0
0
0
Reg_Com
0:
Process Data Communication
0
Reserved
Table 26: Status Byte S1
Status Byte S1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg_Com
ERR_2
ERR5V
TEMP_2 LOAD_2 COM_2
OVR_2
UNR_2
UNR_2
Undershooting underrange limiting value channel 2.
0:
Underrange limiting value is not undershot.
1:
Underrange limiting value is undershot.
OVR_2
Exceeding overrange limiting value channel 2.
0:
Overrange limiting value is not exceeded.
1:
Overrange limiting value is exceeded.
COM_2
Output driver error 1 (COM) channel 2, common mode overrange.
This bit is set if the 24V field power falls below 20 V.
0:
No output driver error 1 (COM)
1:
Output driver error 1 (COM) present.
LOAD_2
Output driver error 2 (LOAD) channel 2, load error.
This bit is set if there is a short circuit during voltage output or if there is an
open circuit during current output.
0:
No output driver error 1 (LAST).
1:
Output driver error 2 (LAST) present.
TEMP_2
Output driver error 3 (TEMP) channel 2, overtemperature.
This bit is set if the permissible temperature of the output driver is exceeded.
0:
No output driver error 3 (TEMP)
1:
Output driver error 3 (TEMP) present.
ERR5V
Error 5V system voltage.
0:
5 V system voltage OK
1:
5 V system voltage less than 4.65 V
ERR_2
Group error channel 2
If one of the channel-related status bits is activated, this bit is also set to 1.
0:
No group error.
1:
Group error present.
Reg_Com
0:
Process data communication.