Содержание 750-556

Страница 1: ...Fieldbus Independent I O Modules 2 AO DC 10 V 750 556 Manual Version 1 0 2 ...

Страница 2: ... 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be fully ex cluded we would appreciate any information or ideas at any time E Mail documentation wago com We wish to point out that the software and hardware terms as well as the tra demarks of companie...

Страница 3: ...se 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Analog Output Modules 7 2 1 1 750 556 2 AO DC 10 V 7 2 1 1 1 View 7 2 1 1 2 Variations 7 2 1 1 3 Description 8 2 1 1 4 Display Elements 9 2 1 1 5 Schematic Diagram 9 2 1 1 6 Technical Data 10 2 1 1 7 Process Image 11 2 1 1 7 1 Standard Format 12 2 1 1 7 2 Special Formats 12 ...

Страница 4: ...nufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual is exclusively geared to special ists having qualifications in PLC programming electrical specialists or per sons instructed by electrical specialists who are also familiar with the valid standards W...

Страница 5: ...ration ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient use of the device and software optimization More information References on additional literature manuals data sheets and INTERNET pages 1 3 Number Notation Number Code Example Note Decimal 100 norma...

Страница 6: ...the ESD information is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembled in housings cabinets or in electrical operation rooms Access must only be given via a key or tool to authorized qualified personnel The relevant valid and applicable standards and guidelin...

Страница 7: ...ntacts Function AO 2 Function AO 1 AO 1 Shield screen Shield screen Common ground Common ground Fig 2 1 1 1 2 Channel Analog Output Module 750 556 g055600e 2 1 1 2 Variations Item No Designation Description 750 556 2 AO 10 V 2 Channel Analog Output Module 10 V 750 556 000 200 2 AO 10 V with Siemens S5 FB 251 2 Channel Analog Output Module 10 V adapted data format for S5 control systems with the us...

Страница 8: ... when snapped onto the DIN rail The input signal is electrically isolated and will be transmitted with a resolu tion of 12 bits The operational readiness and the trouble free internal data bus communica tion of the channels are indicated via a function LED Any configuration of the output modules is possible when designing the field bus node Grouping of module types is not necessary The voltage sup...

Страница 9: ... trou ble free operational readiness off No operational readiness or the internal data bus communication is interrupted 13 14 C D B A C A Fig 2 1 1 2 Display Elements g055202x C green 2 Function AO 2 on Operational readiness and trou ble free operational readiness 2 1 1 5 Schematic Diagram Shield screen AO 1 AO 2 AO 10nF 270pF A D Logic Function Shield screen Common ground Common ground 1 2 3 4 5 ...

Страница 10: ...1 of the full scale value Temperature coefficient 0 01 K of the full scale value Isolation 500 V Field System Bit width 2 x 16 bits data 2 x 8 bits control status option Dimensions mm W x H x L 12 x 64 x 100 from upper edge of 35 DIN rail Weight ca 55 g Standards and Regulations cf Chapter 2 2 of the Coupler Controller Manual EMC Immunity to interference CE acc to EN 50082 2 96 EMC Emission of int...

Страница 11: ...als WAGO I O SYSTEM 750 which you can find on the CD ROM ELECTRONICC Tools and Docs Item No 0888 0412 or in the internet under www wago com Documentation WAGO I O SYSTEM 750 Sys tem Description 2 1 1 7 Process Image The analog output module 750 556 and its variations transmit 16 bit data and 8 status bits per channel The digitalized output value is transmitted in a data word 16 bits as output byte...

Страница 12: ...000 0000 0000 0x6000 24576 0x00 10 0 0111 1111 1111 1111 0x7FFF 32767 0x00 2 1 1 7 2 Special Formats To digitalize the output value the variation 750 550 000 200 uses a data for mat adapted for the S5 control systems using FB 251 For this variation the numerical values ranging from 0xC000 to 0x4000 are scaled on the output voltage ranging from 10 V to 10 V Process values of module 750 556 000 200 ...

Страница 13: ...750 556 2 AO DC 10 V 13 Process Image WAGO I O SYSTEM 750 I O Modules ...