![WAGO 750-508/040-000 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/wago/750-508-040-000/750-508-040-000_manual_3215025033.webp)
WAGO-I/O-SYSTEM 750 XTR
Process Image
33
750-508/040-000 2DO 24 VDC 2A/ Diagn XTR
Manual
Version 1.3.0
4
Process Image
Mapping of process data in the process image of fieldbus systems
The representation of the process data of some I/O modules or their variations in
the process image depends on the fieldbus coupler/controller used. Please take
this information from the section
“I/O Modules” included in the description
concerning the process image of the corresponding coupler/controller.
Table 21: Output Bits
Bit 1
Bit 0
DO 2
DO 1
DO 1
Signal state DO 1
– Digital output channel 1
DO 2
Signal state DO 2
– Digital output channel 2
Table 22: Input Bits
Bit 1
Bit 0
DIAG 2
DIAG 1
DIAG 1
0:
Normal operation, output DO 1 follows the output bit.
1:
Error at output DO 1:
a) No load connected or
b) Short circuit with GND or
c) Short circuit with 24 V or
d) Overtemperature at overload
DIAG 2
0:
Normal operation, output DO 2 follows the output bit.
1:
Error at output DO 2:
a) No load connected or
b) Short circuit with GND or
c) Short circuit with 24 V or
d) Overtemperature at overload