WAGO 750-502 Скачать руководство пользователя страница 1

 

 

 

Fieldbus Independent 
I/O Modules 

2 DO AC/DC 230 V SSR, 0.3 A 
750-509  

Manual 

 
Version 1.0.3 

Содержание 750-502

Страница 1: ...Fieldbus Independent I O Modules 2 DO AC DC 230 V SSR 0 3 A 750 509 Manual Version 1 0 3 ...

Страница 2: ...0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be fully ex cluded we would appreciate any information or ideas at any time E Mail documentation wago com We wish to point out that the software and hardware terms as well as the trademarks of companie...

Страница 3: ...nded Use 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Digital Output Module 7 2 1 1 750 509 2 DO AC DC 230 V SSR 0 3 A 7 2 1 1 1 View 7 2 1 1 2 Description 7 2 1 1 3 Display Elements 8 2 1 1 4 Schematic Diagram 9 2 1 1 5 Technical Data 9 2 1 1 6 Process Image 10 2 1 2 Contact Protective Circuit for Relay Modules 11 ...

Страница 4: ...nufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual is exclusively geared to specialists having qualifications in PLC programming electrical specialists or persons instructed by electrical specialists who are also familiar with the valid standards WAG...

Страница 5: ...ration ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient use of the device and software optimization More information References on additional literature manuals data sheets and INTERNET pages 1 3 Number Notation Number Code Example Note Decimal 100 norma...

Страница 6: ...nformation is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembled in housings cabinets or in electrical operation rooms Access must only be given via a key or tool to authorized qualified personnel The relevant valid and applicable standards and guidelines concer...

Страница 7: ...rs or AC loads The module has two output channels Two actuators with ground earth wire may be directly connected to signal output DO 1 N and PE earth potential or signal output DO 2 N and PE The module is equipped with two high performance MOSFETs as switching relays The semiconductor outputs of the MOSFETs allow for the unlimited triggering of the actuators while having no wear on the outputs The...

Страница 8: ...individual I O modules by means of power jumper contacts Warning The maximum current of the internal power jumper contacts is 10 A When configuring the system it is important not to exceed the maximum sum current However if such a case should occur another supply module must be added Note For the protection of relay coils and contacts inductive loads must be dampened with an effective protection c...

Страница 9: ...al max 10 mA Switching voltage AC DC 0 V 230 V Switching current 300 mA Peak current 0 5 A 20 s 1 5 A 0 1 s Switching rate max 5 Hz 24 V 0 3 A DF 50 0 5 Hz 230 V 0 3 A DF 50 Pull in time typ 4 0 ms Pull in time max 10 ms Dropout time typ 0 1 ms Dropout time max 3 0 ms RON typ 2 1 Ω RON max 3 2 Ω Overvoltage protection AC 275 V Varistor Isolation 1 5 kVeff System Supply 2 5 kV rated surge voltage o...

Страница 10: ... BV Bureau Veritas DNV Det Norske Veritas Cl B GL Germanischer Lloyd Cat A B C D KR Korean Register of Shipping LR Lloyd s Register Env 1 2 3 4 NKK Nippon Kaiji Kyokai RINA Registro Italiano Navale CULUS UL1604 Class I Div2 ABCD T4A KEMA II 3 G EEx nC II C T4 Conformity Marking More Information Detailed references to the approvals are listed in the document Overview Approvals WAGO I O SYSTEM 750 w...

Страница 11: ...ffective Attenuation Advantages Disadvantages Diode UD Load g051211e long yes UD no Advantages easy implementation cost effective reliable uncritical dimensioning low induction voltage Disadvantages attenuation only via load resistor long off delay Series connection diode zener diode UZD Load g051212e medium to short yes UZD no Advantages uncritical dimensioning Disadvantages attenuation only abov...

Страница 12: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastraße 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com ...