WAGO-I/O-SYSTEM 750
Commissioning 63
750-496 8AI 0/4-20mA S.E.
Manual
Version
1.2.2
Click the button to expand the
Status Messages
window at the bottom of the
parameterization dialog to display the status messages.
Figure 28: Expanding the Status Messages Window
The following status messages with corresponding additional information are
displayed:
Table 32: Status Messages – Possible Status Messages with Additional Information
Status message
Error type
Channel
Status byte
Measurement range overflow
Warning
x
0x42
Measurement range underflow
Warning
x
0x41
User-defined limiting value
overrange
Warning
x
0x04
User-defined limiting value
underrange
Warning
x
0x08
Short circuit
Error
x
0x50
Information
x
0x00
Wire break
Error
x
0x60
Information
x
0x00
Channel deactivated
Information
x
0x00
Measured values in permissible
range
Information
x
0x00
The status messages are displayed with assignment of the relevant I/O module
channels.
Figure 29: Status Messages in the Application Window of the Parameterization Dialog
Click the
[Delete]
button to clear the status message history. The history is
automatically cleared if you interrupt the connection to the I/O module or close
the parameterization dialog.