302 Appendix
WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
Table 123: Parameter 45 (Supported by Firmware Versions 05 and above)
Parameter 45 – Mutual Inductance M
RC
for Rogowski Coils
Function
Data Type Access
Factory Setting
Mutual Inductance M for Rogowski Coils
UINT
RW
0x1900 (dec.6400)
0 … 15: 0…65535: Mutual inductance with a resolution of 0.01 nH / LSB
6400:
64.00 nH (factory setting)
Table 124: Parameter 46 (Supported by Firmware Versions 05 and above)
Parameter 46 – Primary Voltage, Voltage Transformer VT
Function
Data Type Access
Factory Setting
Primary Voltage, Voltage Transformer VT
UINT
RW
0x0AD2 (dec.2770)
0 … 15: 0:
invalid
1…65535: Primary voltage of the voltage transformer * VT scaling
2770:
(factory setting)
The scaling of the primary voltage is set in parameter 43, bit 4 and is either0.1 V
per LSB or 1 V per LSB.
Table 125: Parameter 47 (Supported by Firmware Versions 05 and above)
Parameter 47 – Secondary Voltage, Voltage Transformer VT
Function
Data Type Access
Factory Setting
Secondary Voltage, Voltage Transformer VT
UINT
RW
0x0AD2 (dec.2770)
0 … 15: 0:
invalid
1…65535: Primary voltage of the voltage transformer × VT scaling
2770:
(factory setting)
The scaling of the secondary voltage is set in parameter 43, bit 4 and is
either0.1 V per LSB or 1 V per LSB.
The SAG level depends on the nominal input voltage level.
For secondary voltage setting
-
≤
120 V
RMS
, the SAG level is U
LN
= 30 V
RMS
- > 120 V
RMS
the SAG level is U
LN
= 60 V
RMS
With a secondary voltage setting of
-
≤
120 V
RMS
, the nominal input voltage is U
LN
=
200 V
RMS
-
> 120 V
RMS
, the nominal input voltage is U
LN
=
400 V
RMS