Use in Hazardous Environments
WAGO-I/O-SYSTEM 750
750-484 2 AI 4-20 mA HART Ex i
Manual
V 1.2.0 HW-Version 04, SW-Version 03
Figure 42: Text Detail – Marking Example for Approved Ex i I/O Module According to NEC 505
Table 45: Description of Marking Example for Approved Ex i I/O Module According to NEC 505
Marking
Description
CI I,
Explosion protection group
Zn 2
Area of application
AEx
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
Figure 43: Text Detail – Marking Example for Approved Ex i I/O Module According to NEC 506
Table 46: Description of Marking Example for Approved Ex i I/O Modules According to NEC 506
Marking
Description
CI I,
Explosion protection group
Zn 2
Area of application
AEx
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)