Device Description
WAGO-I/O-SYSTEM 750
750-484 2 AI 4-20 mA HART Ex i
Manual
V 1.2.0 HW-Version 04, SW-Version 03
Table 3: Types of Application
Types of Application for the HART I/O Module
1
Programmable fieldbus controllers can communicate with HART devices
from IEC61131-3 programs using the "WagoLibHART_0x.lib" PLC library.
2
Up to 4 HART dynamic variables (PV, SV, TV, QV) can be incorporated in
the cyclic process image of the 750-333 PROFIBUS Coupler or 750-833
PROFIBUS Controller by parameterization via GSD (device master data) or
WAGO-I/O-CHECK 2.
3
When using the 750-333 PROFIBUS DP/V1 Coupler or 750-833
PROFIBUS Controller and the 759-360 PROFIBUS/HART Gateway DTM,
FDT tool routing is possible to the DTM of the connected HART device.
The operating status of the channels is indicated by a green status LED per
channel.
A red fault LED per channel indicates a wire break or that the signal is outside the
measuring range.
The meaning of the LEDs is described in the “Display Elements” section.
Any configuration of the I/O module is possible within an intrinsically safe
segment when configuring the fieldbus node. An arrangement in groups within the
group of potentials is not necessary.
The HART I/O module can be used with all couplers and controllers of the
WAGO-I/O-SYSTEM 750 listed in the following table “Compatibility List”.