WAGO-I/O-SYSTEM 750

2 AI 4-20 mA 12 Bit S.E. HART

750-482

2-Channel-Analog Input Module 4-20 mA HART

V 1.1.0

 

Содержание 750-482

Страница 1: ...Manual WAGO I O SYSTEM 750 2 AI 4 20 mA 12 Bit S E HART 750 482 2 Channel Analog Input Module 4 20 mA HART V 1 1 0 ...

Страница 2: ...t Phone 49 0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always appreciate any information or suggestions for improving the documentation E Mail documentation wago com We wish to point out that the software and hardware terms as w...

Страница 3: ... 10 2 2 Safety Advice Precautions 11 3 Device Description 13 3 1 View 16 3 2 Connectors 17 3 3 Display Elements 18 3 4 Schematic Diagram 19 3 5 Technical Data 20 3 5 1 Device Data 20 3 5 2 Supply 20 3 5 3 Communication 20 3 5 4 Inputs 20 3 6 Approvals 21 3 7 EMC Standards 21 4 Assembly 22 4 1 Assembly Sequence 22 4 2 Inserting and Removing Devices 23 4 2 1 Inserting I O Module 23 4 2 2 Removing th...

Страница 4: ...50 333 833 with Dynamic Variables 52 8 4 FDT DTM with the PROFIBUS DP V1 750 333 750 833 55 8 4 1 Communication on 750 333 833 via FDT DTM 55 8 4 2 Commisioning on a 750 333 833 via FDT DTM 56 9 Process Image 64 9 1 2 AI 4 20 mA 6 Byte Mailbox 65 9 2 2 AI 4 20 mA 1 HART Variable per Channel 67 9 3 2 AI 4 20 mA 2 HART Variables per Channel 68 9 4 2 AI 4 20 mA 3 HART Variables per Channel 69 9 5 2 A...

Страница 5: ...r Dokumentation Hinweis zur Dokumentation Busklemmen 750 xxxx 4 mod_1237986979656_21 doc 29023 The I O module 750 482 shall only be installed and operated according to the instructions in this manual and in the manual for the used fieldbus coupler controller NOTICE Consider power layout of the WAGO I O SYSTEM 750 In addition to these operating instructions you will also need the manual for the use...

Страница 6: ... or serious injury WARNING Personal Injury Indicates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Personal Injury Indicates a low risk potentially hazardous situation which if not avoided may result in minor or moderate injury NOTICE Damage to Property Indicates a potentially hazardous situation which if not avoided may result...

Страница 7: ...0 mA 12 Bit S E HART Manual V 1 1 0 Information Additional Information Refers to additional information which is not an integral part of this documentation e g the Internet Pos 6 4 Dokumentation allgemein Gliederungselemente Seitenwechsel 3 mod_1221108045078_0 doc 21810 ...

Страница 8: ...ont Conventions Font typ e Indicates italic Names of paths and data files are marked in italic type e g C Programme WAGO I O CHECK Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item from a menu e g File New Input Designation of input or optional fields are markeded in bold letters e g Start of measurement range Value Input o...

Страница 9: ...0 xxxx 3 mod_1224061208046_21 doc 24063 2 1 2 Personnel Qualifications All sequences implemented on Series 750 devices may only be carried out by electrical specialists with sufficient knowledge in automation The specialists must be familiar with the current norms and guidelines for the devices and automated environments All changes to the coupler or controller should always be carried out by qual...

Страница 10: ...and firmware are permitted exclusively within the framework of the various alternatives that are documented in the specific manuals WAGO Kontakttechnik GmbH Co KG will be exempted from any liability in case of changes in hardware or software as well as to non compliant usage of components Please send your request for modified and new hardware or software configu rations directly to WAGO Kontakttec...

Страница 11: ...allverhütungsvorschriften beachten 6 mod_1260180657000_21 doc 46735 Pos 9 10 4 Alle Serien Allgemeine Module Wichtige Erläuterungen Sicherheitshinweise Gefahr Auf normgerechten Anschluss achten 6 mod_1260180753479_21 doc 46739 Pos 9 11 1 Alle Serien Allgemeine Module Wichtige Erläuterungen Sicherheitshinweise Achtung Defekte oder beschädigte Geräte austauschen 6 mod_1260180857358_21 doc 46743 NOTI...

Страница 12: ...onnection lines Avoid reverse polarity of data and power supply lines as this may damage the devices involved Pos 9 11 6 Alle Serien Allgemeine Module Wichtige Erläuterungen Sicherheitshinweise Achtung Elektrostatische Entladung vermeiden 6 mod_1260181364729_21 doc 46759 NOTICE Avoid electrostatic discharge The devices are equipped with electronic components that you may destroy by electrostatic d...

Страница 13: ...die keine eigene Spgvers besitzen können direkt anges 5 mod_1245851295034_21 doc 35943 Dabei Two conductor transducers which do not have their own power supply such as adjustable resistances pressure flow and level meters can be connected directly Pos 12 8 Serie 750 WAGO I O SYSTEM Gerätebeschreibung Beschreibung Anwendung Anwendung 750 04xx Diese Messumformer werden dann direkt aus der Busklemme ...

Страница 14: ...8_21 doc 25023 Note Use potential feed module for Ground earth The I O module has no power contacts for PE intake and transfer Use a potential feed module when a PE feed is needed for the subsequent I O modules Pos 12 17 Serie 750 WAGO I O SYSTEM Gerätebeschreibung Beschreibung Versorgung Achtung Maximaler Strom Leistungskontakte 10 A 3 mod_1226499143500_21 doc 25029 NOTICE Do not exceed maximum c...

Страница 15: ...ers 750 806 04 09 8 1 LON Programmable Fieldbus Controllers 750 819 xx 09 8 1 Fieldbus Coupler 750 333 12 ab 13 8 2 3 4 PROFIBUS Programmable Fieldbus Controllers 750 833 12 ab 10 8 1 2 3 4 BACnet Programmable Fieldbus Controllers 750 830 01 01 8 1 KNX Programmable Fieldbus Controllers 750 849 xx ab 01 8 1 Other Fieldbus Coupler Controller on request Functions 1 WAGO I O PRO CAA CoDeSys PLC librar...

Страница 16: ...No Designation Meaning Details see chapter 1 Group marking carrier retractable with additional marking possibility on two miniature WSB markers 2 A B E F Status LEDs Device Description Display Elements 3 Data Contacts Assembly Inserting and Removing Devices 4 1 2 4 5 6 8 CAGE CLAMP Connections Inputs HART 1 2 and Screen Connect Devices Connecting a conductor to the CAGE CLAMP 5 Power Jumper Contac...

Страница 17: ...ngsklemmen Anschlüsse 750 0482 6 mod_1255360323250_21 doc 42565 Table 6 Connectors Connector Meaning HART 1 Sensor 1 Connection HART HART 2 Sensor 2 Connection HART HART 1 Sensor 1 Connection HART HART 2 Sensor 2 Connection HART Power Jumper Contacts 24 V Field Supply 24 V Power Jumper Contacts 0 V Field Supply 0 V E1 E2 S S 750 482 0 V 24 V 24 V 0 V HART 2 HART 1 HART 2 HART 1 S S Figure 2 Connec...

Страница 18: ...ion Don t care 1 x flashing Power On Hardware and software initialization On continously Don t care Ready for operation Power on completed successfully internal data bus communication Don t care On Error Wire break short circuit overload C D green Function HART 2 red Error HART 2 Channel 2 state Description Don t care 1 x flashing Power On Hardware and software initialization On continously Don t ...

Страница 19: ... 4 Schematic Diagram Pos 24 Serie 750 WAGO I O SYSTEM Gerätebeschreibung Schematische Schaltbilder Analogeingangsklemmen Schematisches Schaltbild 750 0482 6 mod_1255433507703_21 doc 42588 750 482 1 2 3 4 5 6 7 8 0 V HART HART A D I 0 V 24 V HART HART 10nF 270pF Shield screen Shield screen Function Error Logic Firgure 4 Schematic Diagram Pos 25 Dokumentation allgemein Gliederungselemente Seitenwech...

Страница 20: ... sensor supply Input current 65 mA Input voltagemax 24 V Input voltage drop Imeas 28 mA not linear as protected against overload U 0 9 V 270 Ω x Imeas Isolation 500 V system supply 3 5 3 Communication Table 10 Technical Data Communication Data width 2 x 2 bytes data or 2 x 2 bytes data 2n x 4 bytes data n number of dynamic variables or 2 x 2 bytes data 6 bytes mailbox 3 5 4 Inputs Table 11 Technic...

Страница 21: ...oc 24020 CULUS UL508 Pos 31 Alle Serien Allgemeine Module Zulassungen Ex i Zulassungen cULus UL1604 Class I Div2 ABCD T4A nur Serie 750 6 mod_1255687238416_0 doc 42994 CULUS UL1604 nur Serie 750 Class I Div2 ABCD T4A Pos 32 Alle Serien Allgemeine Module Überschriften für alle Serien EMV Normen Überschrift 2 4 mod_1242804031875_21 doc 33646 3 7 EMC Standards Pos 33 Serie 750 WAGO I O SYSTEM Geräteb...

Страница 22: ...to prevent injury Pos 38 3 Serie 750 WAGO I O SYSTEM Wichtige Erläuterungen Sicherheitshinweise Achtung Busklemmen in vorgegebener Reihenfolge stecken 6 mod_1256194177073_21 doc 43429 NOTICE Connect the I O modules in the required order Never plug bus modules from the direction of the end terminal A ground wire power contact which is inserted into a terminal without contacts e g a 4 channel digita...

Страница 23: ...ding Ground Conductor in manual System Description WAGO I O SYSTEM 750 Pos 38 9 Alle Serien Allgemeine Module Wichtige Erläuterungen Sicherheitshinweise Achtung Arbeiten an Geräten nur spannungsfrei durchführen 6 mod_1256193963573_21 doc 43426 NOTICE Perform work on devices only if the system is de energized Working on devices when the system is energized can damage the devices Therefore turn off ...

Страница 24: ...previous or possibly subsequent I O module are established Pos 38 11 Serie 750 WAGO I O SYSTEM Montieren Busklemme entfernen 4 mod_1239169375203_21 doc 30334 4 2 2 Removing the I O Module 1 Remove the I O module from the assembly by pulling the release tab Figure 7 Removing the I O module Electrical connections for data or power contacts are disconnected when removing the I O module Pos 39 Dokumen...

Страница 25: ...e single connection If more than one conductor must be routed to one connection these must be connected in an up circuit wiring assembly for example using WAGO feed through terminals Exception If it is unavoidable to jointly connect 2 conductors then you must use a ferrule to join the wires together The following ferrules can be used Length 8 mm Nominal cross section max 1 mm2 for 2 conductors wit...

Страница 26: ...the following graphic shows an example of the connection view and the circuit diagrams of the potential feed module 750 614 which is required to connect passive 3 conductor HART sensors as well as active HART sensors and of the HART I O module 750 482 0 230V 0V 750 614 1 5 2 6 3 7 4 8 750 482 4 8 HART HART HART 1 HART1 S E1 E2 13 14 C D S S 750 482 HART 2 HART 2 S 13 14 C D B A 750 614 0 230 V 0V ...

Страница 27: ...sor 5 2 1 2 Connecting a 3 Conductor HART Sensor To connect one or two passive 3 conductor HART sensors to the HART module 750 482 a WAGO potential amplification module item number 750 604 or 750 614 must be connected upstream for the 0V potential The HART and HART sensors are connected to the HART and HART terminal points of the HART module 750 482 The passive sensors are supplied with 24VDC dire...

Страница 28: ...sors to the HART module 750 482 a WAGO potential amplification module item number 750 604 or 750 614 is used as with the passive 3 conductor HART sensors Commensurate with the HART sensor voltage 24VDC or 230VAC the HART sensors are fed either directly from the potential amplification module with 24VDC or externally with 230VAC In both cases the potential amplification module provides the 0V poten...

Страница 29: ... 24 VDC AO 4 20 mA HART AO 4 20 mA HART 0 VDC Figure 12 Connecting an active 24VDC HART sensor 5 2 2 2 Connecting an active 230VAC HART Sensor C D B A 13 14 C D B A 750 614 E1 E2 13 14 C D S S 750 482 HART Sensor AO 4 20 mA HART AO 4 20 mA HART 230 VAC external Figure 13 Connecting an active 230VAC HART sensor Pos 45 Dokumentation allgemein Gliederungselemente Seitenwechsel 3 mod_1221108045078_0 d...

Страница 30: ...tion Further advantages of HART are simple construction maintenance and application as well as flexible data access via up to two operator control units PC and hand terminal HART field devices and also HART masters are compatible with 4 20 mA technology HART field devices can therefore be used with non HART compatible masters and vice versa This provides the great advantage that the user can upgra...

Страница 31: ...ith HART dynamic variables 2 AI acyclic PROFIBUS services PROFIBUS DP V1 Fieldbus coupler 750 333 or Fieldbus controller 750 833 4 with PROFIBUS HART Gateway 759 360 see chapter Compatibily List Pos 47 5 Serie 750 WAGO I O SYSTEM Funktionsbeschreibung Funktionsbeschreibung 750 0482 0484 Einstellung mit I O CHECK bis Schritt 5 6 mod_1256128722664_21 doc 43371 In the as supplied state the HART Modul...

Страница 32: ...rs of the HART I O module using WAGO I O CHECK 2 when the default operating mode 2AI 6 byte mailbox has been changed to the PROFIBUS operating mode 2 AI acyclic PROFIBUS services and is then to be changed back to the default mode Changing to a PROFIBUS mode or between PROFIBUS modes is typically carried out within a PROFIBUS system using GSD in preference Note Restriction of Settings for PROFIBUS ...

Страница 33: ... and under Port COM1 Communications port Then confirm this selection by clicking OK 4 Switch on the supply voltage to your coupler controller 5 When the coupler controller has booted up click Identify on the toolbar The set up of your fieldbus node will be automatically detected and shown graphically in the node view and also in the navigation bar as a tree structure Pos 47 6 Serie 750 WAGO I O SY...

Страница 34: ...482 0484 Einstellung über GSD Einleitung 6 mod_1256129716781_21 doc 43396 When the parameters have been set successfully this will be indicated by a message Figure 16 WAGO I O CHECK message for successfully parameterizing Information Additional Information about WAGO I O CHECK You will find a detailed description of the functions and use of the commissioning tool in the 759 302 WAGO I O CHECK 2 ma...

Страница 35: ...g the parameters however the components of the PROFIBUS system which define the structure of the input and output process image must first be configured The GSD files for PROFIBUS are read in or installed by the configuration software used These provide the characteristic device data necessary for configuration particulars of their communications capability and other information The size of the pr...

Страница 36: ... click on the button with three points in the UsrPrm User Parameter column Depending on the selected operating mode various set up options which are listed in the following tables are provided in the dialog box which then opens Pos 47 9 Serie 750 WAGO I O SYSTEM Funktionsbeschreibung Funktionsbeschreibung 750 0482 Screenshot Modulkonfiguration 6 mod_1256201305868_21 doc 43443 ...

Страница 37: ...HART Manual V 1 1 0 75x 482 2AI 4 20 mA SE Figure 18 Parameterization dialog for selecting 75x 482 2AI 4 20 mA SE Pos 47 10 Serie 750 WAGO I O SYSTEM Funktionsbeschreibung Funktionsbeschreibung 750 0482 0484 Parameter für alle Betriebsmodi 6 mod_1256201435421_21 doc 43446 ...

Страница 38: ...nsbeschreibung 750 0482 ZwÜberschrift Parameter für die Auswahl 75x 482 2AI 1 2 3 x2 HV 6 mod_1256201560567_21 doc 43449 Selection Parameters for 75x 482 2AI 1 2 3 x2 HV Pos 47 12 Serie 750 WAGO I O SYSTEM Funktionsbeschreibung Funktionsbeschreibung 750 0482 0484 Tabelle Parameterdaten für die HART Variablen 6 mod_1256201746138_21 doc 43455 Table 15 Parameter Data for the HART Variables Parameter ...

Страница 39: ...43467 7 2 FDT DTM Concept FDT is an abbreviation for Field Device Tool This is frame application software which can be used to parameterize configure and control fieldbus devices separately from the specific communication technologies of the different fieldbusses In order to establish communication with the individual devices in an FDT application and from there to be able to access the adjustable...

Страница 40: ...205491526_21 doc 43480 WAGO provides gateway DTMs for PROFIBUS 759 360 Profibus HART Gateway DTM and MODBUS TCP 759 359 ModbusTCP HARTGatewayDTM for this purpose WAGOframe Gateway HART Sensor xy DTM HART Sensor Fieldbus Firgure 19 FDT DTM communication principle Information Additional Information about the Download of the HARTGatewayDTMs The gateway DTMs for PROFIBUS 759 360 Profibus HARTGatewayDT...

Страница 41: ...ART client application HART comm HART device HART server HART comm HART communication Figure 20 Operation of HART devices via PROFIBUS 8 Description of Operation The principle of operation of the HART I O module is described in more detail in the following sub sections with regard to the various types of application and operating modes Application type 1 Operation with PLC library WagoLibHART_0x l...

Страница 42: ...r of modules Because of the process data capacity of the HART I O module please be sure to take into account the corresponding maximum number of modules that can be connected when using a WAGO 75x xxx coupler controller You can find this number in the list in section Compatibility List In the cyclic process image of the coupler controller the HART I O module looks like a 1 channel I O module whose...

Страница 43: ... 5 Analog Channel2 Dummy Figure 21 Communication by means of WagoLibHART_0x lib using a 75x 8xx Controller as an example Information Additional Information for the Application You can read a detailed description with a clear application example for the library WagoLibHART_0x lib with WAGO I O PRO CAA in the appropriate application note which describes the HART application using this library You wi...

Страница 44: ...ng WAGO I O CHECK 2 Note Restriction of Settings for PROFIBUS Operating Mode This changeover and operation with other than a PROFIBUS Coupler 750 333 or Controller 750 833 is not yet possible at the present time for PROFIBUS operating modes 2 AI 1 2 3 or 4 HART variables per channel A HART I O module that has once been set up for HART dynamic variables using GSD files can therefore currently only ...

Страница 45: ...eschreibung 750 0482 FDT DTM mit dem 750 841 ETHERNET Controller 6 mod_1256212473728_21 doc 43502 8 2 FDT DTM with the 750 841 ETHERNET Controller In the default mode 2AI 6 byte mailbox when the HART I O module is connected to a 750 841 WAGO ETHERNET TCP IP Controller it is also possible to carry out HART communication by means of the FDT DTM frame application WAGOframe Note Consider the maximum n...

Страница 46: ...ModbusTCP HARTGatewayDTM 759 359 can be downloaded from the WAGO website at www wago com Service Downloads AUTOMATION 8 2 1 Communication on 750 841 via FDT DTM The ModbusTCP HARTGatewayDTM 759 359 and the DTM for the connected HART sensor are embedded in the WAGOframe FDT DTM frame application Communication from the WAGOframe FDT DTM frame application to the connected HART sensor takes place in t...

Страница 47: ... Name Description Item No 1 WAGO I O CHECK optional Commissioning tool for the WAGO I O SYSTEM 750 759 302 2 Default prg Special boot project for Ethernet controllers Application note number A116101 Download www wago com 3 WAGOframe FDT frame application for parameterization commissioning and diagnostics of devices with DTM device drivers 759 370 4 WAGO_Modbus_TCP _DTM DTM for MODBUS TCP 5 WAGO_07...

Страница 48: ...troller 750 833 It is then possible to restore the default state of the HART I O module using WAGO I O CHECK 2 and the PROFIBUS Coupler 750 333 or Controller 750 833 When doing so it must be ensured that the parameters of the PROFIBUS Coupler 750 333 or Controller 750 833 are not set using GSD files 2 Set up an FTP connection to the Ethernet controller The easiest way to do this is using Internet ...

Страница 49: ...the mouse to Network in the tree structure and click on Add in the context menu right mouse button Select WAGO Modbus TCP in the dialog which opens and confirm the selection by clicking OK The entry MODBUS TCP_DTM will now be added to the tree structure 11 Click Set up connection on the Device menu The entry MODBUS TCP_DTM will now be changed to italics in the tree structure 12 Move the mouse to M...

Страница 50: ...Next go to Set up connection on the Device menu The entry ModbusCommChannel 075x 08xx DTM will now be changed to italics in the tree structure 16 Next go to More functions on the Device menu and click on Device list on the sub menu A dialog window with a list of devices will open Click on Update After a while the DTM s for the connected HART devices will now also be shown in green 17 Move the mous...

Страница 51: ...0 333 or Controller 750 833 You can find this number in the list in the section Compatibility List With PROFIBUS it is possible to evaluate and process further information in addition to the actual measured signal which is output in the main variables This additional information is then output accordingly by means of the HART dynamic variables Some HART field devices sensors provide such additiona...

Страница 52: ...es from the HART devices Communication on PROFIBUS takes place by means of the acyclic PROFIBUS DP V1 commands A prerequisite for the implementation of cyclic communication is the successful start up of cyclic data traffic The final transfer of data between the HART I O module and the connected sensor then takes place using the HART on Profibus protocol Parameterization monitoring of the HART devi...

Страница 53: ...ng description of the configuration is by way of example You will find the exact steps for configuring your PROFIBUS system in the documentation for the software used 1 As is typical for a PROFIBUS application set up the required operating mode 2 AI 1 2 3 or 4 HART variables per channel using the GSD files You will find more detailed information on this in the section Setting the Operating Mode Pa...

Страница 54: ...to the operating modes You will find a description of the different entries with a list of all the associated parameters in the section Setting the Operating Mode Parameters Setting Up via GSD Figure 26 HW Config in STEP7 10 Select the entry corresponding to the required operating mode and incorporate this into your configuration 11 Double clicking on a module in the configuration tree structure w...

Страница 55: ...ule please be sure to take into account the corresponding maximum number of modules that can be connected when using a WAGO PROFIBUS DP V1 Coupler 750 333 or Controller 750 833 You can find this number in the list in section Compatibility List Information Additional Information about WAGOframe and Profibus HARTGatewayDTM The FDT DTM frame application WAGOframe can be ordered under Item No 759 370 ...

Страница 56: ...T I O module and the connected sensor then takes place using the HART on Profibus protocol WAGOframe PROFIBUS HARTGateway DTM 759 360 HART Sensor xy DTM HART Sensor 750 333 750 482 Mode 7 PROFIBUS KBUS H A R T Figure 27 Example of a FDT DTM Communication via PROFIBUS 8 4 2 Commisioning on a 750 333 833 via FDT DTM This section describes the most important steps for commissioning the HART I O modul...

Страница 57: ... in the section Setting the Operating Mode Parameters Setting Up via GSD Alternatively you can also open WAGO I O CHECK 2 if available In this case proceed as described in the section Setting the Operating Mode Parameters Setting via WAGO I O CHECK 2 2 Open WAGOframe in Expert mode 3 Next make sure that the Device catalog dialog window is shown on the right hand side of the screen This must be act...

Страница 58: ... 9 Move the mouse once again to the device type name of your PROFIBUS master in the tree structure and select it by clicking with the left mouse button Next go to More functions on the Device menu and click on Device list on the sub menu A dialog window with a list of devices will open Figure 28 Dialog window Device list 10 Select the device with the address 126 by clicking on it and click Change ...

Страница 59: ...ration and identify for Slot 2 Slot x which module is physically plugged in to its fieldbus node Pay attention to all I O modules that deliver process data in the process image Slot 1 has been predefined with the fieldbus coupler controller For module configuration a drop down menu of all available I O modules can be found in the Module column After the node configuration is complete confirm by cl...

Страница 60: ...tion register Module Configuration 13 Select the register Parameterization and open a dialog view in which you can make additional parameter changes Confirm the changes made here by clicking Accept Figure 31 Dialog window 750 333 Configuration register Parameterization 14 When configuration is completed close the configuration dialog window ...

Страница 61: ...ed module number corresponds to the slot in the structure module 01 is the bus coupler The right side contains the parameterization dialog for this module 17 Set the desired parameter for each channel separately such as the analog filter time for the input channel 10 640 ms the simulation mode activation and the simulation value setting with the overflow or underflow selection When the simulation ...

Страница 62: ... OK A further view will appear in the dialog window in which you can now select the channel to which your HART device is connected Figure 34 Channel selection dialog window 21 Select M01_Ch01 for Channel 1 of the first plugged in HART module or M01_Ch02 for Channel 2 Confirm the selection by clicking OK Depending on the entry M01_Ch01 HART DTM or M01_Ch01 HART DTM will be added in the tree structu...

Страница 63: ...will be shown in green Figure 35 Dialog window Device list Update 24 Move the mouse to the entry for the channel to which your HART device is connected in the tree structure and double click it a dialog window with the online parameterization will then open After a short time connection symbols will be displayed after the respective parameters Pos 48 Dokumentation allgemein Gliederungselemente Sei...

Страница 64: ... data of some I O modules or their variations into the process image is specific to the fieldbus coupler controller used This information as well as the specific configuration for relevant control status bytes is located in the section Fieldbus Specific Configuration of Process Data This section describes the process image of the particular coupler controller For pure 4 20 mA analog values the HAR...

Страница 65: ... 11 00 0x7FFC 32764 0x00 off 22 0111 1111 1111 11 01 0x7FFD 32765 0x42 on Status bits F Cable Break O Overrun 9 1 2 AI 4 20 mA 6 Byte Mailbox In the 2AI 6 byte mailbox operating mode the HART module provides the fieldbus coupler controller with a 12 byte input and output process image via one logical channel 1 control byte C0 and 1 status byte S0 are used to monitor the data flow The data is mappe...

Страница 66: ...ata Channel 2 Table 24 Output Process Image Output Process Image Offset Designation of bytes Remark 0 C0 Controlbyte 1 Internal Use used internally 2 3 4 5 6 7 MBX_REQ Mailbox request data 8 9 10 11 not used Tabelle 25 Control byte C0 Control byte C0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Tabelle 26 Status byte S0 Statusbyte S0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 General fault...

Страница 67: ...when one HART dynamic variable per channel is incorporated optionally PV SV TV QV the PROFIBUS telegram has a size of 12 bytes Table 27 PROFIBUS Telegram 1 HART Variable per Channel PROFIBUS Telegram 1 Variable per Channel Offset Designation of Bytes Remark 0 1 AI0 Analog input data Channel 1 2 3 4 5 HV0_0 1st HART variable Channel 1 6 7 AI1 Analog input data Channel 2 8 9 10 11 HV1_0 1st HART var...

Страница 68: ... incorporated optionally PV SV TV QV the PROFIBUS telegram has a size of 20 bytes Table 28 PROFIBUS Telegram 2 HART Variables per Channel PROFIBUS Telegram 2 Variables per Channel Offset Designation of Bytes Remark 0 1 AI0 Analog input data Channel 1 2 3 4 5 HV0_0 1st HART variable Channel 1 6 7 8 9 HV0_1 2nd HART variable Channel 1 10 11 AI1 Analog input data Channel 2 12 13 14 15 HV1_0 1st HART ...

Страница 69: ...IBUS telegram has a size of 28 bytes Table 29 PROFIBUS Telegram 3 HART Variables per Channel PROFIBUS Telegram 3 Variables per Channel Offset Designation of Bytes Remark 0 1 AI0 Analog input data Channel 1 2 3 4 5 HV0_0 1st HART variable Channel 1 6 7 8 9 HV0_1 2nd HART variable Channel 1 10 11 12 13 HV0_2 3rd HART variable Channel 1 14 15 AI1 Analog input data Channel 2 16 17 18 19 HV1_0 1st HART...

Страница 70: ...RT Manual V 1 1 0 9 5 2 AI 4 20 mA 4 HART Variables per Channel With the PROFIBUS DP V1 Fieldbus Coupler 750 333 or Fieldbus Controller 750 833 when four HART dynamic variables per channel are incorporated optionally PV SV TV QV the PROFIBUS telegram has a size of 36 bytes ...

Страница 71: ... 0 1 AI0 Analog input data Channel 1 2 3 4 5 PV0 Primary variable Channel 1 6 7 8 9 SV0 Secondary variable Channel 1 10 11 12 13 TV0 Tertiary variable Channel 1 14 15 16 17 QV0 Quaternary variable Channel 1 18 19 AI1 Analog input data Channel 2 20 21 22 23 PV1 Primary variable Channel 2 24 25 26 27 SV1 Secondary variable Channel 2 28 29 30 31 TV1 Tertiary variable Channel 2 32 33 34 35 QV1 Quatern...

Страница 72: ...O module Information Additional Information about PROFIBUS DP V1 750 333 or 750 833 You can read a detailed description of this in the PROFIBUS DP V1 Fieldbus Coupler 750 333 manual or Fieldbus Controller manual in the section 750 333 Fieldbus Coupler or 750 833 Fieldbus Controller Configuring and Parameterizing the I O Modules Analog I O Modules 2 AI Modules You will find these manuals on the Int...

Страница 73: ...for downloading the library The library can be downloaded from the WAGO Internet site at www wago com Service Documentation left navigation bar WAGO Software 759 WAGO I O PRO CoDeSys right column Additional Information Libraries WagoLibHART_03 lib or by entering the following into the address bar of the web browser http www wago com wagoweb documentation app_note libraries WagoLibHA RT_03 lib Info...

Страница 74: ...O I O SYSTEM Einsatz in Ex Bereichen Kennzeichnung 3 mod_1224157499140_21 doc 24182 11 1 Identification Pos 54 4 Serie 750 WAGO I O SYSTEM Einsatz in Ex Bereichen Kennzeichnung für Europa gemäß CENELEC und IEC 3 mod_1224157620203_21 doc 24185 11 1 1 For Europe according to CENELEC and IEC Figure 36 Example for lateral labeling of bus modules Figure 37 Printing on text detail in accordance with CEN...

Страница 75: ...ding to NEC 500 Figure 38 Example for lateral labeling of bus modules Figure 39 Printing on text detail in accordance with CENELEC and IEC Table 35 Description of Printing on Printing on Text Description CL 1 Explosion protection group condition of use category DIV 2 Area of application zone Grp ABCD Explosion group gas group Optemp code T4 Temperature class Pos 54 7 Dokumentation allgemein Gliede...

Страница 76: ...allation Regulations in Germany DIN VDE 0100 Installation in power plants with rated voltages up to 1000 V DIN VDE 0101 Installation in power plants with rated voltages above 1 kV DIN VDE 0800 Installation and operation in telecommunication plants including information processing equipment DIN VDE 0185 lightning protection systems The USA and Canada have their own regulations The following are exc...

Страница 77: ...device when power is off and only in a non hazardous area Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous When a fuse is provided the following marking shall be provided A switch suitable for the location where the equipment is installed shall be provided to remove the power from the fuse The switch need not be integrated in the equipment For...

Страница 78: ...paratus category M2 the apparatus shall be erected in an enclosure that ensures a sufficient protection according to directive 94 9 EC A Declaration of Conformity according to annex X of the directive 94 9 EC shall certify the correct installation of the devices named above into an enclosure or a control cabinet If interface circuits are operated without the 750 3 fieldbus coupler DEMKO 08 ATEX 14...

Страница 79: ...en used in the presence of combustible dust the enclosure shall comply with the relevant requirements of IEC 61241 0 2004 and IEC 61241 1 2004 Installation addition removal or replacement of modules fieldbus connectors or fuses may only take place when the system supply and the field supply are switched off or when the area is known to be non hazardous DIP switches binary switches and potentiomete...

Страница 80: ...ple 40 Figure 20 Operation of HART devices via PROFIBUS 41 Figure 21 Communication by means of WagoLibHART_0x lib using a 75x 8xx Controller as an example 43 Firgure 22 WAGO I O PRO project with incorporated library WagoLibHART_0x lib 45 Figure 23 FDT DTM Communication via MODBUS TCP IP 47 Figure 24 ftp access on a fieldbus controller 48 Figure 25 System overview with a PROFIBUS fieldbus coupler c...

Страница 81: ...ia PLC Library 44 Table 18 Software required for the Commissioning on a 750 841 via FDT DTM 47 Table 19 Operating Mode for PROFIBUS DP V1 51 Table 20 Software required for the Commissioning on a 750 333 833 with Dynamic Variables 53 Table 21 Software required for the Commissioning on a 750 333 833 via FDT DTM 57 Table 22 Process Values for the HART Module 65 Table 23 Input Process Image 66 Table 2...

Страница 82: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastraße 27 D 32423 Minden Phone 49 5 71 8 87 0 Fax 49 5 71 8 87 1 69 E Mail info wago com Internet http www wago com ...