WAGO I/O SYSTEM 750 XTR
Appendix 67
750-481/040-000 2AI RTD Ex i XTR
Manual
Version 1.1.0
8.1.2.2 PROFIBUS DP Fieldbus Couplers/Controllers
750-333(/0xx-000), 750-833(/0xx-000)
The aforementioned fieldbus couplers/controllers allow channel- and module-
specific behavior parameterization during diagnostics.
Table 41: General Module/Channel Parameters
Parameter
Value
Explanation
Diagnostics
Channel x
(x = 0 … 1)
The fieldbus coupler/controller signals a diagnosis
if one of the following events:
•
External error
•
Measurement range underflow
•
Line break
are reported by at least one I/O module channel.
0 (lock)
*)
Diagnostics reported by the I/O module do not
lead to the signaling of a diagnosis by the fieldbus
coupler/controller.
1 (release)
Diagnostics reported by the I/O module lead to
the signaling of a diagnosis by the fieldbus
coupler/controller.
*)
Default setting