42
Process Image
WAGO-I/O-SYSTEM 750 XTR
750-469/040-000 2AI Thermocouple configurable /XTR
Manual
Version 1.3.0
Table 34: Process Image mV Measurement ±30 mV
Voltage
mV
Numeric value
1)
Status
byte
hex.
LED
error
AI 1, 2
Binary
Hex.
Dec.
<
−30.0
’0000.0000.0000.0000’
0000
0
0x00
OFF
−30
’1011 0110 1100 0010’
B6C2
−18750
0x00
OFF
−20
’1100 1111 0010 1100’
CF2C
−12500
0x00
OFF
−10
’1110 0111 1001 0110’
E796
−6250
0x00
OFF
−5
’1111 0011 1100 1011’
F3CB
−3125
0x00
OFF
0
’0000 0000 0000 0000’
0000
0
0x00
OFF
5
’0000 1100 0011 0101’
0C35
3125
0x00
OFF
10
’0001 1000 0110 1010’
186A
6250
0x00
OFF
20
’0011 0000 1101 0100’
30D4
12500
0x00
OFF
30
’0100 1001 0011 1110’
493E
18750
0x00
OFF
> 30.0
>’0100.1001.0011.1110’
> 0x493E
> 18750
0x00
OFF
Wire break
’0111.1111.1111.1111’
0x7FFF
32767
0x00
OFF
1)
Voltage values below 0 mV are represented in two's complement binary.