Commissioning 67
750-458 8AI; TC; Adjust
Manual
Version 1.3.0
Table 37:
Scaling
Menu Item
Option
Description
Channel x
Activate user scaling
User scaling is activated. By enabling this setting, you can also
specify the individual gain and offset values.
*)
User scaling is deactivated. Individually specified gain and
offset values cannot be entered.
Gain
The Gain value changes the gain factor of the unscaled process value.
The value entered must fall in the value range of 0 … 65535.
The resolution is 1/1024.
Offset
The offset value shifts the zero point of the unscaled process value (shift
along the Y axis).
The value entered must fall in the value range of −32768
… 32767.
Process value
The process value is displayed for the channel selected (see section
“Startup” > … > “Start” Tab). The unit depends on the sensor type
selected (see section “Startup” > … > “Channel settings”). For voltage
measurements, the process value is output in mV, for temperature
measurements in °C.
If the channel is deactivated, “N/A” (not available) is displayed.
This value is read cyclically from the I/O module.
*)
Factory setting
Содержание 750-458
Страница 1: ...Manual 750 458 8AI TC Adjust 8 Channel Analog Input Module Thermocouple Adjustable Version 1 3 0 ...
Страница 63: ...Commissioning 63 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 23 Channel settings Menu Item View ...
Страница 66: ...66 Commissioning 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 24 Scaling Menu Item View ...
Страница 69: ...Commissioning 69 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 25 Calibration Menu Item View ...