WAGO-I/O-System 750
Appendix 191
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
Pos: 94 /Serie 750 ( WAGO-I/O-SYST EM)/Anhang/R ecord-Datensätze ( Par ametrierung) (370) @ 23\mod_1433334035308_21.docx @ 183392 @ 2 @ 1
14.3 Record Data Sets
The following table contains all available fieldbus data sets sorted by data set
index. Indices 0x0000 … 0x7FFF can be used according to the manufacturer
specifications. In this range, the parameter sets specific to the I/O module or
fieldbus coupler fall on indices 0x2000 and 0x4000.
All indices from 0x8000 are standardized. More information about the structure of
the standardized datasets is available in the PROFINET IO specification
More information on record data sets!
You can read more about special record data sets in the context of diagnostics. The
structure of standardized diagnostic data sets and channel-specific diagnostics are
explained in the section “Channel-Specific Diagnostics”.
Table 160: Record Data Sets
Index
[hex]
Data set
Access
Level
2000
Submodule parameter
(administrated by I/O module)
r/w
Submodule
4000
Submodule parameter
(administrated by fieldbus coupler)
w
*)
8000 ExpectedIdentificationData for one sub-slot
r
Submodule
8001 RealIdentificationData for one sub-slot
r
800A Diagnosis in channel coding
r
800B Diagnosis in all codings
r
800C Diagnosis, Maintenance, Qualified and Status
r
8010 Maintenance required in channel coding
r
8011 Maintenance demanded in channel coding
r
8012 Maintenance required in all codings
r
8013 Maintenance demanded in all codings
r
8028 RecordInputDataObjectElement
r
8029 RecordOutputDataObjectElement
r
802A PDPortDataReal
r
802B PDPortDataCheck
r/w
802F PDPortDataAdjust
r/w
8071 PDInterfaceAdjust
r/w
8072 PDPortStatistic
r
8080 PDInterfaceDataReal
r
AFF0 I&M0
r
C000 ExpectedIdentificationData for one slot
r
Module
C001 RealIdentificationData for one slot
r
C00A Diagnosis in channel coding
r
C00B Diagnosis in all codings
r