94 Commissioning
WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
8.3
Assigning the IP Address to the Fieldbus Node
The IP address must occur in the network only once!
For error-free network communication, note that the assigned IP address must
occur only once in the network!
In the event of an error, the error message “IP address configuration error” (error
code 6 – error argument 7) is indicated by 'I/O' LED at the next power-on.
•
Use
address selection switch
(DIP switch) to assign IP address
(manually).
•
Automatic assignment of addresses via DHCP
(
IP address via the fieldbus)
•
Assigning IP Address via
“
WAGO Ethernet Settings”
(static IP address via the serial communication port or the ETHERNET
interface)
•
Assigning IP Address via
BootP
(IP address via the fieldbus)
8.3.1
Assigning IP Address via Address Selection Switch
Use the address selection switch to set the host ID, which is the last byte of the
IP address, with values between 1 and 254 binary coded.
The first three bytes of the IP address are specified by the fieldbus coupler/
controller. The fieldbus coupler/controller uses a static base IP address to assign
the IP address via the address selector switch.
The basic IP address can be changed via the Web-based management or
WAGO Ethernet settings (in the delivery state:
192.168.1.0
).
The subnet mask and default gateway values are taken from the static settings
(as delivered: subnet mask =
255.255.255.0
, default gateway =
0.0.0.0
).
Example:
Base IP address:
192.168.1.0
Set DIP switch value:
50
(binary coded: 00110010)
Resulting IP address:
192.168.1.
50