144 Diagnostics
WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
Table 64: Blink Code Table for the I/O LED Signaling, Error Code 6
Error Code 6: " Configuration error, node configuration"
Error
Argument
Error Description
Solution
1
Invalid MAC ID
1. Turn off the power supply of the node.
2. Replace the head station.
3. Turn on again the power supply of the node.
2
Ethernet Hardware
initialization error
1. Restart the head station by turning the power supply off and
on again.
2. If the error still exists, replace the head station.
3
TCP/IP initialization
error
1. Restart the head station by turning the power supply off and
on again.
2. If the error still exists, replace the head station.
4
Network configuration
error (no IP Address)
1. Check the settings of DHCP/BootP server or if a static IP
address is used.
5
Application protocol
initialization error
2. Restart the head station by turning the power supply off and
on again.
3. If the error still exists, replace the head station.
6
Maximum process
image size exceeded
1. Turn off the power supply of the node.
2. Reduce number of I/O modules.
3. Turn on again the power supply of the node.
7
Double IP address in
network
1. Change configuration. Use another IP address, which is not
yet present in network.
2. Restart the head station by turning the power supply off and
on again.
8
Error when building
the process image
1. Turn off the power supply of the node.
2. Reduce number of I/O modules.
3. Restart the head station by turning the power supply off and
on again.
4. If the error still exists, replace the head station.
9
Error when mapping
the I/O modules to a
fieldbus
1. Check the file „io_config.xml“ on the head station.
Table 65: Blink Code Table for the I/O LED Signaling, Error Code 7
Error Code 7: „Not supported I/O module“
Error
Argument
Error Description
Solution
n
First not supported
I/O module at
position n
1. Turn off the power supply for the node.
2. Replace the (n+1) I/O module with process data or reduce
the number of I/O modules until the (n+1) I/O module.
3. Turn the power supply on.
Table 66: Blink Code Table for the I/O LED Signaling, Error Code 8 … 11
Error Code 8 … 11: - not used -
Error
Argument
Error Description
Solution
-
Not used
-