Fieldbus Coupler • 55
Fieldbus Coupler 750-346
WAGO-I/O-SYSTEM 750
DeviceNet
4. DIP switches 7 and 8 are used to set the desired baud rate.
Baud rate
DIP7
DIP8
125 kBaud
*)
OFF
OFF
250 kBaud
ON
OFF
500 kBaud
OFF
ON
not allowed
ON
ON
ON
12
34
5
ON
67
8
8
7
6
5
4
3
2
1
g012551x
Fig. 3-11: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) of the
station with MAC ID 1.
*)
Presetting
5. Then switch on the coupler supply voltage.
3.1.7.3 Configuration with Static Assembly
In this example, the software WAGO
NETCON
is used for the configuration.
The node in the example consists of the following I/O modules:
1
2
3
4
5
6
7
DI DI
DODO
402
516
516
516
467
550
600
DODO DODO AI AI
AO AO
1
2
3
4
5
6
7
8
ON
Fig. 3.1.7-12 Example Fieldbus node
g012554x
1. Starting Software and EDS file load
6. Start the configuration software WAGO NETCON.
7. Load an EDS file for the fieldbus coupler in WAGO NETCON, i. e. "750-
346.EDS".
For this click on "File/ Copy EDS" and choose the EDS-file to load.
Note
You can download the EDS files for the fieldbus coupler from the Internet
under: www.wago.com.
8. Upon downloading the EDS file into WAGO NETCON, you can create a new
project and start configuring your network.