222 Appendix
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
Table 178: Parameters of the PROFIsafe V2 I/O modules with iPar Server functionality
(PSAFE_V2_iPar)
PSAFE_V2_iPar
Representative of the PSAFE_V2_iPar:
750-661/000-003, 75x-662/000-003,
75x-666/000-003, 75x-667/000-003
Parameterization data length in bytes
Standard parameterization
Structured parameterization
21
25
Parameter
Settings
Description
Scope
Terminal is physically
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) set to zero or filtered by the
fieldbus coupler
plugged
*)
•
supplied by the I/O module or output to the
periphery.
Diagnosis
The diagnostic information of the corresponding
channel is
Channel
disabled
*)
•
not transmitted to the PROFIBUS DP master.
enabled
•
transmitted to the PROFIBUS DP master
F_Check_SeqNr
In the CRC calculation, the sequence number is
Module
Check
•
included.
NoCheck
*)
•
not included.
F_Check_iPar
Individual parameters in the F parameter field
Module
NoCheck
*)
•
are not checked.
F_SIL
The safety requirement level is
Module
SIL3
*)
•
SIL3.
F_CRC_Length
Die F_CRC has a length of
Module
3-Byte-CRC
*)
•
3 bytes.
F_Block_ID
The ID of the F parameter field is
Module
1
*)
•
1.
F_Par_Version
The PROFIsafe layer is operated in
Module
V2-mode
*)
•
PROFIsafe V2 mode.
F_Source_Add
The F source address can accept the following
values:
Module
1
… 65534
1
… 65534
F_Dest_Add
The F destination address can accept the
following values:
Module
1
… 65534
•
1
… 65534
F_WD_Time
The F monitoring time can accept the following
values:
Module
50
… 150
*)
… 10000
•
50
… 10000 ms
F_iPar_CRC
The CRC of the individual parameter set can
accept the following values:
Module
0
*)
… 65535
•
0
… 65535
*)
Default settings