WAGO I/O SYSTEM 750 XTR
Appendix 203
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
Table 155: Parameters of the 2, 4, 8 and 16-channel digital output modules (DO)
2DO, 4DO, 8DO, 16DO
Representatives of the 2DO:
75x-501, 75x-502, 75x-509,´75x-512, 75x-513,
75x-514, 75x-517, 75x-535,
Representatives of the 4DO:
75x-504, 75x-516, 75x-519, 75x-531, 75x-540,
Representatives of the 8DO:
75x-530, 75x-534, 75x-536, 75x-1515, 75x-1516,
Representatives of the 16DO:
750-1500, 75x-1501, 750-1504, 75x-1505
Parameterization data length in bytes
Standard parameterization
Structured parameterization
3 (4
1)
)
7 (8
1)
)
Parameter
Settings
Description
Scope
Terminal is physically
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) filtered by the fieldbus coupler.
plugged
*)
•
output to the periphery.
Substitute value
If, in the event of a PROFIBUS DP fault, the
switching of substitute values is enabled, within
the fieldbus coupler parameterization, this value is
transmitted to the periphery in the event of a fault.
Channel
0
*)
1
*)
Default settings
1)
Applies to 16DO
The following table shows the parameterization properties of the 1, 2, 4 and 8-
channel digital output modules with asynchronous diagnostic properties.
Table 156: Parameters of the 1, 2, 4 and 8-channel digital output modules (DO_DIA)
1DO_1DIA, 1DO_1PI-DIA,
2DO_2DIA, 2DO_2PI-DIA,
2DO_4DIA, 2DO_4PI-DIA,
4DO_4DIA, 4DO_4PI-DIA
8DO_8DIA, 8DO_8PI-DIA
Representatives of the 1DO_1DIA or 1DO_1PI-DIA:
75x-523,
Representatives of the 2DO_2DIA or 2DO_2PI-DIA:
75x-507, 75x-508, 75x-522,
Representatives of the 2DO_4DIA or 2DO_4PI-DIA:
75x-506,
Representatives of the 4DO_4DIA or 4DO_4PI-DIA:
75x-532,
Representatives of the 8DO_8DIA or 8DO_8PI-DIA:
75x-537
Parameterization data length in bytes
Standard parameterization
Structured parameterization
3 (4
1)
)
7 (8
1)
)
Parameter
Settings
Description
Scope
Terminal is physically
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) filtered by the fieldbus coupler or
set to zero.
plugged
*)
•
output to the periphery.
Map diagnosis to input PI
2)
The diagnostic information of the I/O module is
Module
disabled
*)
•
not mapped into the input process image.
Enabled
•
mapped into the input process image.
Diagnosis
The diagnostic information of the corresponding
channel is
Channel
disabled
*)
•
not transmitted to the PROFIBUS DP
master.
enabled
•
transmitted to the PROFIBUS DP master.