WAGO I/O System 750 XTR 

 

 

 

750-1516/040-000  

8DO 24 VDC 0.5A LSS 2-wire XTR 

8-Channel Digital Output; 24 VDC; 0.5 A;  

Low-Side Switching; 2-Wire Connection; Extreme 

Version 1.0.0  

 

 

 

Содержание 750-1516/040-000

Страница 1: ...Manual WAGO I O System 750 XTR 750 1516 040 000 8DO 24 VDC 0 5A LSS 2 wire XTR 8 Channel Digital Output 24 VDC 0 5 A Low Side Switching 2 Wire Connection Extreme Version 1 0 0...

Страница 2: ...Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always appreciate any info...

Страница 3: ...afety Advice Precautions 12 3 Device Description 16 3 1 View 18 3 2 Connectors 19 3 2 1 Data Contacts Local Bus 19 3 2 2 Power Jumper Contacts Field Supply 20 3 2 3 Push in CAGE CLAMP Connectors 22 3...

Страница 4: ...roup 45 7 2 2 Examples of Connection 46 8 Use in Hazardous Environments 47 8 1 Marking Configuration Examples 48 8 1 1 Marking for Europe According to ATEX and IECEx 48 8 1 2 Marking for the United St...

Страница 5: ...tem 750 XTR and in the manual for the used fieldbus coupler controller Consider power layout of the WAGO I O System 750 XTR In addition to these operating instructions you will also need the system de...

Страница 6: ...y Indicates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if n...

Страница 7: ...otes about this Documentation 7 750 1516 040 000 8DO 24 VDC 0 5A LSS 2 wire XTR Manual Version 1 0 0 Additional Information Refers to additional information which is not an integral part of this docum...

Страница 8: ...and data files are marked in italic type e g C Program Files WAGO Software Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item...

Страница 9: ...troller should always be carried out by qualified personnel with sufficient skills in PLC programming 2 1 3 Use of the 750 Series in Compliance with Underlying Provisions Fieldbus couplers controllers...

Страница 10: ...Specified Devices The devices to be supplied ex works are equipped with hardware and software configurations which meet the individual application requirements These modules contain no parts that can...

Страница 11: ...ronic equipment sent to your local collection point Improper disposal of electrical and electronic equipment can be harmful to the environment and human health 2 1 4 1 2 Packaging Packaging contains m...

Страница 12: ...tection against contact Prevent fire from spreading outside of the enclosure Offer adequate protection against UV irradiation Guarantee mechanical stability Restrict access to authorized personnel and...

Страница 13: ...nt temperatures allow it to cool off before touching it System supply only with appropriate fuse protection Without overcurrent protection the electronics can be damaged For 24 V system supply input v...

Страница 14: ...per electrical contact between the DIN rail and device is necessary to maintain the EMC characteristics and function of the device Replace defective or damaged devices Replace defective or damaged dev...

Страница 15: ...electrostatic discharge per DIN EN 61340 5 1 3 When handling the devices please ensure that environmental factors personnel work space and packaging are properly grounded Use only direct current DC f...

Страница 16: ...f the I O module can be damaged by the induced voltage produced when inductive loads are de activated An appropriate protection circuit e g a recovery diode must be installed in parallel to the load t...

Страница 17: ...s the individual modules can be arranged in any combination when configuring the fieldbus node An arrangement in groups within the group of potentials is not necessary Mixed operation Mixed operation...

Страница 18: ...Legend for Figure View Pos Description Details See Section 1 Marking possibility with Mini WSB 2 Status LEDs Device Description Display Elements 3 Data contacts Device Description Connectors 4 Push i...

Страница 19: ...which are available as self cleaning gold spring contacts Figure 2 Data Contacts Do not place the I O modules on the gold spring contacts Do not place the I O modules on the gold spring contacts in o...

Страница 20: ...efully to prevent injury Do not touch the blade contacts The I O module 750 1516 040 000 has 2 self cleaning power jumper contacts that supply and transmit power for the field side The contacts on the...

Страница 21: ...urrent that can flow through the power jumper contacts is 10 A The power jumper contacts can be damaged and the permissible operating temperature can be exceeded by higher current values When configur...

Страница 22: ...Table 5 Legend for Figure Push in CAGE CLAMP Connectors Channel Designation Connector Function 1 DO 1 1 Output DO 1 Signal voltage 24 V 9 Output DO 1 Field supply 24 V 2 DO 2 2 Output DO 2 Signal volt...

Страница 23: ...Display Elements Table 6 Legend for Figure Display Elements Channel Designation LED State Function 1 State DO 1 1 Off Output DO 1 Signal voltage 0 Green Output DO 1 Signal voltage 1 8 State DO 8 8 Off...

Страница 24: ...24 Device Description WAGO I O System 750 XTR 750 1516 040 000 8DO 24 VDC 0 5A LSS 2 wire XTR Manual Version 1 0 0 3 5 Schematic Diagram Figure 6 Schematic Diagram...

Страница 25: ...24 VDC 25 30 via power jumper contacts power supply via blade contact transmission via spring contact Derating must be observed Derating supply voltage For 40 55 C For 55 70 C Surrounding air tempera...

Страница 26: ...Technical Data Climatic Environmental Conditions Surrounding air temperature operation 40 C 70 C Surrounding air temperature storage 40 C 85 C Relative humidity 95 Elevation above sea level without t...

Страница 27: ...for use in Ordinary Location UL E198726 for Use in Hazardous Locations Cl I Div 2 Group A B C D T4 The following Ex approvals are pending for 750 1516 040 000 I O modules T V 17 ATEX 193969 X II 3 G E...

Страница 28: ...XTR Manual Version 1 0 0 The following ship approvals are pending for 750 1516 040 000 I O modules ABS American Bureau of Shipping LR Lloyd s Register Env 1 2 3 4 For more information about the ship...

Страница 29: ...ection Applications ATEX acc Directive 2014 34 EU General Requirements EN 60079 0 Group II electrical equipment Equipment requirements in the types of protection EN 60079 7 Electrical equipment in e t...

Страница 30: ...e EN 50155 EN 61373 Random vibration Category 1 classes A and B Shock 5g 30 ms Category 1 classes A and B Environmental Requirements EN 61850 3 Achieved EN 60721 3 1 1K5 except precipitation and ice f...

Страница 31: ...s EN 61000 6 5 Electromagnetic compatibility EMC Part 6 5 Generic standards Immunity for equipment used in power station and substation environment EN 61850 3 Communication networks and systems for po...

Страница 32: ...ds With Electrical Frequencies EN 61000 4 8 300 A m continous 1000 A m for 1 s Damped Oscillatory Magnetic Fields EN 61000 4 9 1000 A m Ged mpft schwingende Magnetfelder EN 61000 4 10 100 A m Voltage...

Страница 33: ...R Manual Version 1 0 0 Table 16 EMC Testing Standards Immunity to Interference Standard Test Value Shipbuilding Max 2 W DC 3 Veff AC 10 to 15th harmonic 10 1 for 15th to 100th harmonic 1 for 100th to...

Страница 34: ...QP 30 MHz 2 0 GHz 54 dB V m AV 1 0 GHz 6 0 GHz 24 dB V m QP 156 MHz 165 MHz Shipbuilding Class A 80 dB V m 50 dB V m QP 150 kHz 30 MHz 60 dB V m 54 dB V m QP 30 MHz 100 MHz 54 dB V m QP 100 MHz 2 0 GH...

Страница 35: ...3 dB A 43 dB A QP 0 15 MHz 0 5 MHz 40 dB A 30 dB A AV 0 15 MHz 0 5 MHz 43 dB A QP 0 5 MHz 30 MHz 30 dB A AV 0 5 MHz 30 MHz EN 55032 Class B 40 dB A 30 dB A QP 0 15 MHz 0 5 MHz 30 dB A 20 dB A AV 0 15...

Страница 36: ...uctuation voltage 1 4 Un 5 1 1 4 Interruptions of voltage supply S1 5 1 3 Supply change over must be provided by a suitable external power supply unit 5 2 3 Electromagnetic compatibility EN 50121 3 2...

Страница 37: ...DO 5 DO 4 DO 3 DO 2 DO 1 DO 1 Signal state DO 1 Digital output channel 1 DO 2 Signal state DO 2 Digital output channel 2 DO 3 Signal state DO 3 Digital output channel 3 DO 4 Signal state DO 4 Digital...

Страница 38: ...cts are sharp edged Handle the I O module carefully to prevent injury Do not touch the blade contacts Insert I O modules only from the proper direction All I O modules feature grooves for power jumper...

Страница 39: ...ized High voltage can cause electric shock or burns Switch off all power to the device prior to performing any installation repair or maintenance work Temperature range applies to normal operation XTR...

Страница 40: ...d crooked or askew Once the I O module has snapped into place the electrical connections for the data contacts and power contacts if any to the head station or to the preceding and if applicable follo...

Страница 41: ...uctor must be routed to one connection these must be connected in an up circuit wiring assembly for example using WAGO feed through terminals Terminate both solid and stranded or ferruled conductors b...

Страница 42: ...2 Connect Devices WAGO I O System 750 XTR 750 1516 040 000 8DO 24 VDC 0 5A LSS 2 wire XTR Manual Version 1 0 0 6 2 Connection Example Figure 11 Connection Example with Two Actuators on Channels 1 And...

Страница 43: ...n 7 1 Important Notes Only operate interference free I O modules at a safe extra low voltage When using interference free I O modules only use power supplies with protective extra low voltage PELV SEL...

Страница 44: ...fety switching device Reverse supply must absolutely be avoided Avoid short circuits between outputs Short circuits between outputs of different interference free digital output modules must absolutel...

Страница 45: ...safety switching device shall be combined to form a potential group The power supply of the potential group may only be provided via the following supply or filter modules Table 21 Supply or Filter Mo...

Страница 46: ...24 VDC 0 5A LSS 2 wire XTR Manual Version 1 0 0 7 2 2 Examples of Connection 8 Channel Single Pole Power Supply Disconnection Figure 13 8 Channel Single Pole Disconnection Example 8 Channel Double Po...

Страница 47: ...2 hazardous areas and shall be used in accordance with the marking and installation regulations The following sections include both the general identification of components devices and the installatio...

Страница 48: ...50 1516 040 000 8DO 24 VDC 0 5A LSS 2 wire XTR Manual Version 1 0 0 8 1 Marking Configuration Examples 8 1 1 Marking for Europe According to ATEX and IECEx Figure 15 Marking Example per ATEX and IECEx...

Страница 49: ...IC Dust group Explosive dust atmosphere T135 C Maximum surface temperature of the enclosure no dust bin Dc Level of equipment protection EPL Mining I Device group Mining M2 Device category High degree...

Страница 50: ...tem 750 XTR 750 1516 040 000 8DO 24 VDC 0 5A LSS 2 wire XTR Manual Version 1 0 0 Figure 17 Marking Example of an Approved I O Module Ex i per ATEX and IECEx Figure 18 Text Detail Marking Example of an...

Страница 51: ...perature of the enclosure no dust bin Dc Level of equipment protection EPL Mining I Device group Mining M2 M1 Device category High level of safety with circuits that offer a very high level of safety...

Страница 52: ...States of America NEC and Canada CEC Figure 19 Marking Example According to NEC Figure 20 Text Detail Marking Example According to NEC 500 Table 24 Description of Marking Example According to NEC 500...

Страница 53: ...ment protection level EPL Associated apparatus with intrinsic safety circuits for use in Zone 20 IIC Group T4 Temperature class Gc Equipment protection level EPL Figure 22 Text Detail Marking Example...

Страница 54: ...ark nA Type of protection ia IIIC Type of protection and equipment protection level EPL Associated apparatus with intrinsic safety circuits for use in Zone 20 IIC Group T4 Temperature class Gc Equipme...

Страница 55: ...ting when replacing components The product is an open system As such the product must only be installed in appropriate enclosures or electrical operation rooms to which the following applies Can only...

Страница 56: ...in particular Operating DIP switches coding switches or potentiometers Replacing fuses Wiring connecting or disconnecting of non intrinsically safe circuits is only permitted in the following cases T...

Страница 57: ...nected to telephone networks or telecommunication cables WARNING The radio receiver module 750 642 may only be used to connect to external antenna 758 910 WARNING Product components with fuses must no...

Страница 58: ...Potential Group Example 45 Figure 13 8 Channel Single Pole Disconnection Example 46 Figure 14 8 Channel Double Pole Disconnection Example 46 Figure 15 Marking Example per ATEX and IECEx 48 Figure 16...

Страница 59: ...ronmental Conditions and Shipbuilding 30 Table 15 EMC Product and Generic Standards 31 Table 16 EMC Testing Standards Immunity to Interference 32 Table 17 EMc Testing Standards Emission of Interferenc...

Страница 60: ...WAGO GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 571 887 0 Fax 49 571 887 844169 E Mail info wago com Internet www wago com...