30 Device Description
WAGO-I/O-SYSTEM 750 XTR
750-1415/040-000 8DI 24VDC 3ms 2-Wire XTR
Manual
Version 1.3.0
Table 19: EMC – Emission of Interference
Standard
Test Value
*)
Enclosure Emission of Interference
• EN 61000-6-3
• EN 55022 Class B
30 dB(µV/m), QP, 30 MHz … 230 MHz
37 dB(µV/m), QP, 230 MHz … 1 GHz
70 dB(µV/m), Peak, 1 GHz … 3 GHz
50 dB(µV/m), AV, 1 GHz … 3 GHz
74 dB(µV/m), Peak, 3 GHz … 6 GHz
54 dB(µV/m), AV, 3 GHz … 6 GHz
• EN 61000-6-4
• EN 60255-26
• EN 55011 Class A
• EN 55022 Class A
40 dB(µV/m), QP, 30 MHz … 230 MHz
47 dB(µV/m), QP, 230 MHz … 1 GHz
76 dB(µV/m), Peak, 1 GHz … 3 GHz
56 dB(µV/m), AV, 1 GHz … 3 GHz
80 dB(µV/m), Peak, 3 GHz … 6 GHz
60 dB(µV/m), AV, 3 GHz … 6 GHz
• Shipbuilding
**)
(Class B)
80 dB(µV/m) …50 dB(µV/m), QP,
150 kHz … 300 kHz
50 dB(µV/m) … 34 dB(µV/m), QP,
0.3 MHz … 30 MHz
54 dB(µV/m), QP, 30 MHz … 2 GHz
24 dB(µV/m), QP, 156 MHz … 165 MHz
• Shipbuilding
**)
(Class A)
80 dB(µV/m) … 50 dB(µV/m), QP,
150 kHz … 30 MHz
60 dB(µV/m) … 54 dB(µV/m), QP,
30 MHz … 100 MHz
54 dB(µV/m), QP, 100 MHz … 2 GHz
24 dB(µV/m), QP, 156 MHz … 165 MHz
Conducted Emission of Interference – Line Connection AC Voltage
• EN 61000-6-3
• EN 55022 Class B
Standard not applicable
• EN 61000-6-4
• EN 55011 Class A
• EN 50121-3-2
Standard not applicable
Conducted Emission of Interference – Line Connection
• Shipbuilding
**)
(Class B)
96 dB(µV) … 50 dB(µV), 10 kHz … 150 kHz
60 dB(µV) … 50 dB(µV), 150 kHz … 350 kHz
50 dB(µV), 0.35 MHz … 30 MHz
• Shipbuilding
**)
(Class A)
120 dB(µV) … 69 dB(µV), 10 kHz … 150 kHz
79 dB(µV), 150 kHz … 500 kHz
73 dB(µV), 0.5 MHz … 30 MHz