2857-570/024-001
Functions
42
Product manual | Version: 2.0.0
3-Phase Power Measurement Module, 1 A
Table 38: Parameter 10 – Current Transformer Ratio, Neutral Conductor
Address
0x005B
Data Type
UINT16
Access
R/W
Factory setting
0x0001
Activation: Parameter 2, Bit 15 required
0
not permitted
≥1
Value for the current transformer ratio divisor
Table 39: Parameter 11 – Peak Value Measurement Observation Interval, Phase 1
Address
0x0060
Data Type
UINT16
Access
R/W
Factory setting
0x0014
0 … 19
not permitted
20 … 254
Number of half waves for measuring peak values
≥255
not permitted
Table 40: Parameter 12 – Peak Value Measurement Observation Interval, Phase 2
Address
0x0061
Data Type
UINT16
Access
R/W
Factory setting
0x0014
0 … 19
not permitted
20 … 254
Number of half waves for measuring peak values
≥255
not permitted
Table 41: Parameter 13 – Peak Value Measurement Observation Interval, Phase 3
Address
0x0062
Data Type
UINT16
Access
R/W
Factory setting
0x0014
0 … 19
not permitted
20 … 254
Number of half waves for measuring peak values
≥255
not permitted
Table 42: Parameter 14 – Overvoltage Threshold Value, Phase 1
Address
0x0064
Data Type
FLOAT
Access
R/W
Factory setting
410 V
0
The overvoltage threshold check is deactivated.
≥1
Overvoltage Threshold (max. 440 V)
Table 43: Parameter 15 – Overvoltage Threshold Value, Phase 2
Address
0x0066
Data Type
FLOAT
Access
R/W
Factory setting
410 V
0
The overvoltage threshold check is deactivated.
≥1
Overvoltage Threshold (max. 440 V)
Table 44: Parameter 16 – Overvoltage Threshold Value, Phase 3
Address
0x0068
Data Type
FLOAT
Access
R/W
Factory setting
410 V
0
The overvoltage threshold check is deactivated.
≥1
Overvoltage Threshold (max. 440 V)
Table 45: Parameter 17 – Overcurrent Threshold Value, Phase 1
Address
0x006A
Data Type
FLOAT
Access
R/W
Factory setting
550 A
0
The overvoltage threshold check is deactivated.
≥1
Overcurrent Threshold (max.100000 A)