2857-570/024-001
Functions
Product manual | Version: 2.0.0
41
3-Phase Power Measurement Module, 1 A
Table 30: Parameter 3 – Undervoltage Threshold, Phase 1
Address
0x0050
Data Type
FLOAT
Access
R/W
Factory setting
0 V
0
Checking if undervoltage threshold is deactivated.
≥1
Value for Undervoltage Threshold (max. 440 V)
Table 31: Parameter 4 – Undervoltage Threshold, Phase 2
Address
0x0052
Data Type
FLOAT
Access
R/W
Factory setting
0 V
0
Checking if undervoltage threshold is deactivated.
≥1
Value for Undervoltage Threshold (max. 440 V)
Table 32: Parameter 5 – Undervoltage Threshold, Phase 3
Address
0x0054
Data Type
FLOAT
Access
R/W
Factory setting
0 V
0
Checking if undervoltage threshold is deactivated.
≥1
Value for Undervoltage Threshold (max. 440 V)
Table 33: Parameter 6a – Rogowski Coil
Address
0x004F
Data Type
FLOAT
Access
R/W
Factory setting
1
>0
User-defined: Rogowski coil factor must be set.
1
RC70: Rogowski coil factor = 0,07198 µH
2
RC125: Rogowski coil factor = 0,07214 µH
3
RC175: Rogowski coil factor = 0,07231 µH
Table 34: Parameter 6b – Rogowski Coil Factor [µH]
Address
0x0056
Data Type
FLOAT
Access
R/W
Factory setting
0,07198 µH
>0
Factor Value in µH (induction of the coil)
Table 35: Parameter 7 – Current Transformer Ratio, Phase 1
Address
0x0058
Data Type
UINT16
Access
R/W
Factory setting
0x0001
Activation: Parameter 2, Bit 12 required
0
not permitted
≥1
Value for the current transformer ratio divisor (Max. value = 2500)
Table 36: Parameter 8 – Current Transformer Ratio, Phase 2
Address
0x0059
Data Type
UINT16
Access
R/W
Factory setting
0x0001
Activation: Parameter 2, Bit 13 required
0
not permitted
≥1
Value for the current transformer ratio divisor (Max. value = 2500)
Table 37: Parameter 9 – Current Transformer Ratio, Phase 3
Address
0x005A
Data Type
UINT16
Access
R/W
Factory setting
0x0001
Activation: Parameter 2, Bit 14 required
0
not permitted
≥1
Value for the current transformer ratio divisor (Max. value = 2500)