2857-570/024-001
Properties
24
Product manual | Version: 2.0.0
3-Phase Power Measurement Module, 1 A
Property
Description
Factory setting
Data logging
With micro SD memory
cards
Transmission parameter
6)
Bus address
1 … 277
1
Transmission rate
9600 baud
19200 baud
19200 Baud
Number of data bits
8
Number of stop bits
0.5; 1; 2; 2.5
1
Parity
None; Even; Odd
Even
Bus termination
150 Ω; 120 Ω/1 nF; None
None
6)
Can be configured via service interface.
3.6.6 Wiring
CAUTION
Inadequate wire cross sections cause temperature increases!
To avoid increasing thermal risks and risk of injury, only use conductor cross-sections
sufficient for the required maximum load current. The conductor cross-sections specified
in the technical data refer exclusively to the mechanical connection capacity of the clamp-
ing points.
Table 10: Technical Data, Wiring – Expected Environmental Temperature for Connecting Cables
Use in the scope
Temperature of the connecting cables
EN 61010-1
≤ 25 K above the expected max. environmental tem-
perature
UL 61010-1
≥ 95 °C
Table 11: Technical Data ‒ Wiring: WAGO Clamp Series 804
WAGO Clamp Series 804
Voltage Measurement Inputs
;
Supply connection
;
Switch output
Connection technology
Push-in CAGE CLAMP® with Push-button
Solid "s"
0,25 … 2,5 mm² / 20 … 12 AWG
Fine-stranded "f"
0,25 … 2,5 mm² / 20 … 12 AWG
Strip length
10 … 11 mm / 0,39 … 0,43 in
Table 12: Technical Data ‒ Wiring: WAGO Clamp Series 805
WAGO Clamp Series 805
Current Measurement Inputs
Connection technology
Push-in CAGE CLAMP® with Push-button
Solid "s"
0,2 … 1,5 mm² / 24 … 16 AWG
Fine-stranded "f"
0,2 … 1,5 mm² / 24 … 16 AWG
Strip length
9 … 10 mm / 0,35 … 0,39 in
3.6.7 Mechanical Conditions
Observe installation instructions regarding vibration resistance.