2789-9023
Fieldbus Description
Product manual | Version: 1.0.0
29
EtherNet/IP Communication Module
Table 25: Ethernet Link Object – Instance 1 (Port 1)
Attribute
ID
Ac-
cess
Name
Data type Description
Factory set-
ting
1
Get
Interface
Speed
UINT32
Transmission rate
0x0000000A
or
0x00000064
2
Get
Interface
Flags
UINT32
Interface configuration/status information
Dependent
on ETHER-
NET connec-
tion
Bit 0
Link Status
Bit 1
Half/full duplex
Bits 2 … 4
Detection status
Bit 5
Manual settings require reset
Bit 6
Local hardware fault
Bits 7 … 31
Reserved
3
Get
Physical
Address
ARRAY
of 6
UINTs
MAC address
6
Get/
Set
Interface
Control
STRUCT
of:
Configuration of the physical interface
Control Bits UINT16
Interface configuration bits
0x0001
Bit 0
Automatic detection
Bit 1
Specification of duplex mode
Bits 2 … 15
Reserved
Forced In-
terface
Speed
UINT16
Interface speed specified for the interface
0x000A or
0x0064
7
Get
Interface
Type
UINT8
Interface type
0x02 –
Twisted Pair
Value 0
Unknown
Value 1
Internal interface, e.g., in the case of
an integrated switch
Value 2
Twisted pair (e.g., 100BASE-TX)
Value 3
Glass fiber (e.g., 100BASE-FX)
Values 4 …
256
Reserved
8
Get
Interface
Status
UINT8
Interface status
Value 0
Unknown
Value 1
Interface active and ready to send/
receive
Value 2
Interface disabled
Value 3
Interface is testing
Values 4 …
256
Reserved
9
Get/
Set
Admin Sta-
tus
UINT8
Administration status
0x01
Value 0
Reserved
Value 1
Enable interface
Value 2
Disable interface If this is the sole
CIP interface, a request to disable is
acknowledged with an error (error
code 0x09).
Values 3 …
256
Reserved
10
Get
Interface
Label
CHAR[ ]
Name of the interface
“ETH Port 1”