2787-2448
Diagnostics
36
Product manual | Version: 1.0.0
Power Supply Pro 2
8
Diagnostics
8.1 Diagnostics via Indicators
The product has an optical status indicator. This indicator consists of five LEDs.
These LEDs indicate
8
and diagnostics.
Table 41: Display of Diagnostics – Warnings
Indicator
Output Voltage Too Low
Output Voltage Too High
Overload Threshold or Trip-
ping Current of Electronic Cir-
cuit Breaker Exceeded
> 100 %
Flashing (2 Hz)
Flashing (2 Hz)
Flashing (2 Hz)
> 75 %
Off
Flashing (2 Hz)
Signaling of regular utilization
> 50 %
Off
Off
> 25 %
Off
Off
DC OK
Flashing (2 Hz)
Off
Table 42: Diagnostic Indicators – Errors
Indicator
Short Circuit at Out-
put
Overtemperature
Shutdown
1)
Internal Product
Fault
Communication inter-
face
> 100 %
Flashing (8 Hz)
Flashing (8 Hz)
Flashing (8 Hz)
Flashing (8 Hz)
> 75 %
Off
Steady
Flashing (8 Hz)
Off
> 50 %
Off
Off
Flashing (8 Hz)
Off
> 25 %
Off
Off
Flashing (8 Hz)
Off
DC OK
Off
Off
Flashing (8 Hz)
Steady
1)
Automatic restart (factory setting)