2787-2154

Properties

20

Product manual | Version: 1.0.2
Power Supply Pro 2

Property

Value

Output power 

2)

120 W

Power Boost

3.75 A (5 s)

Top Boost

15 A (15 ms)

Derating of output power

See section Derating

Line regulation 

2)

< 0.02 %

Load regulation 

3)

< 1.0 %

Residual ripple/noise 

4)

< 70 mV

Overload behavior 

5) 6)

“Constant Current” Mode 

1)

“Constant Current with Latching Shutdown” Mode

“Hiccup” Mode

“Electronic Circuit Breaker” Mode

“Latching Shutdown on Thermal Overload” Mode

“Power Boost” Mode

“Top Boost” Mode

1)

 Factory setting

2)

 Nominal load, in range 90 … 264 VAC

3)

 10 % / 90 % load step

4)

 20 MHz bandwidth

5)

 See section 

8

 

Short-Circuit and Overload Behavior [

}

 63]

6)

 Can be set via the WAGO Interface Configuration software

7)

 See figure “Turn-on Time”

Overshoot

Turn on Time

Input

Voltage

Output

Voltage

Figure 10: Turn-on Time

!

 NOTICE

Select conductor cross-sections according to current load!

In the event of a fault, the output current of a power supply can be up to 1.5 × I

OUT

. Only

use conductor cross-sections sufficient for the current load!

Table 20: Technical Data – Output Connection

Property

Value

Cross-section

Solid

0.08 … 2.5 mm² / 28 … 12 AWG

Fine-stranded

0.08 … 2.5 mm² / 28 … 12 AWG

Insulated ferrule with plastic collar

0.25 … 1.5 mm² / 20 … 16 AWG

Ferrule without plastic collar

0.25 … 2.5 mm² / 20 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inch

Содержание 2787-2154

Страница 1: ...Product manual Version 1 0 2 Power Supplies Power Supply Pro 2 1 phase 48 VDC 2 5 A 120 W 2787 2154...

Страница 2: ...to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always appreci ate any information or suggestions for improving the documentation E Mail...

Страница 3: ...e label 13 3 4 Label 14 3 5 Connections 14 3 5 1 Connectors 14 3 5 2 Input 15 3 5 3 Output 15 3 5 4 Signal 16 3 6 Indicators 16 3 7 Control Elements 17 3 7 1 Buttons 17 3 8 Communication interface 17...

Страница 4: ...Backstage Tab 41 10 3 1 2 Device Tab 41 10 3 1 2 1 Dialog Settings 41 10 3 1 2 2 Dialog Simulation 51 10 3 2 Main Menu 54 10 3 3 Display Section 54 10 3 3 1 Display Section Measurements 55 10 3 3 2 D...

Страница 5: ...v Power Supply Pro 2 11 5 6 Power Boost Mode 65 11 5 7 Top Boost Mode 66 11 6 Maintenance 67 12 Decommissioning 68 12 1 Disposal and Recycling 68 13 Appendix 69 13 1 Application Notes 69 13 1 1 AC Op...

Страница 6: ...devices The product is an open system and is designed for installation in a additional enclosure The product is designed for use in dry indoor rooms Operation of the products in industrial area is pe...

Страница 7: ...ible for proper installa tion and safety of the system All laws standards guidelines local regulations and ac cepted technology standards and practices applicable at the time of installation and the i...

Страница 8: ...eath or irreversible injury Action step to reduce risk WARNING Type and source of hazard Possible consequences of hazard that also include severe injury Action step to reduce risk CAUTION Type and sou...

Страница 9: ...er The trademarks are listed in the Appendix 8 Protected Rights 71 Subject to Change The instructions guidelines standards etc in this manual correspond to state of the art at the time the documentati...

Страница 10: ...s and practices applicable at the time of installation 2 2 Electrical Safety High voltage can cause electric shock or burns Disconnect all power sources from the product before performing any installa...

Страница 11: ...rized personnel and may only be opened with tools Ensure the required pollution degree in the vicinity of the system Offer adequate protection against direct or indirect contact Offer adequate protect...

Страница 12: ...either via the WAGO USB Communication Cable or via an attached communication module It is also possible to record and evaluate various output parameters via the WAGO Interface Configuration software...

Страница 13: ...8 2 5 IN OUT Ambient Temp Derating www wago com 2787 2154 Class I Equipment Indoor Use Only IP20 Technical Data WAGO Kontakttechnik GmbH Co KG Hansastr 27 32423 Minden Germany www wago com WAGO is a r...

Страница 14: ...nt Details 1 2D data matrix code Contains the information from positions 2 5 2 Key number Fixed information 37S 3 ID number per D U N S Fixed information WAGO Minden 4 WAGO item number or internal SAP...

Страница 15: ...tails Input Connection Series 721 Series see section 8 Accessories 71 Connection Technology CAGE CLAMP 3 5 3 Output 1 2 3 4 5 6 Figure 5 Output X2 Connection Table 8 Legend for Figure Output X2 Connec...

Страница 16: ...r This indicator consists of five LEDs These LEDs indicate operating states and Diagnostics 100 75 50 25 DC OK Figure 7 Optical Status Indicator Table 12 Indication of Operating States General Indicat...

Страница 17: ...ke settings 3 8 Communication interface The communication interface is covered with a cap Remove this cap to use the commu nication interface NOTICE Avoid destruction of the product by electrostatic d...

Страница 18: ...ur PC 3 Carefully insert the plug for the communication interface straight into the communi cation interface in such a way that the keying tab fits into the lower recess The plug is seated correctly o...

Страница 19: ...Mains failure buffering time typ 1 110 VAC 40 ms 230 VAC 40 ms Holding time typ 1 110 VAC 41 ms 230 VAC 41 ms 1 At nominal load Table 18 Technical Data Input Connection Property Value Cross section S...

Страница 20: ...0 load step 4 20 MHz bandwidth 5 See section 8 Short Circuit and Overload Behavior 63 6 Can be set via the WAGO Interface Configuration software 7 See figure Turn on Time Overshoot Turn on Time Input...

Страница 21: ...ol with a partially insulated shaft type 2 see section 8 Accessories 70 3 9 4 Efficiency Power Loss Table 21 Technical Data Efficiency Power Loss Property Value Efficiency typ 1 110 VAC 92 5 230 VAC 9...

Страница 22: ...Isolation voltage See section Safety Table 24 Technical Data Signal Connection Property Value Cross section Solid 0 08 2 5 mm 28 12 AWG Fine stranded 0 08 2 5 mm 28 12 AWG Insulated ferrule with plas...

Страница 23: ...Table 28 Technical Data Product Protection Property Value Internal input fuse 1 T 6 3 A 250 VAC Transient suppression at input Yes varistor Overload protection at output Electronic Overvoltage protec...

Страница 24: ...D D C B PE Digital Output Digital Input Output Figure 13 Dielectric Strength 3 10 Guidelines approvals and standards 3 10 1 Guidelines An EU Declaration of Conformity and CE marking exist for the prod...

Страница 25: ...iated radio frequency electromagnetic field immunity test EN 61000 4 4 Part 4 4 Testing and measurement techniques Electrical fast transient burst immunity test EN 61000 4 5 Part 4 5 Testing and measu...

Страница 26: ...5 min B DC OK digital input digital output 1 kV 5 kHz 100 kHz 5 min B Communication 1 kV 5 kHz 100 kHz 5 min B EN 61000 4 5 Part 4 5 Testing and measurement techniques Surge immunity test L N 1 kV B...

Страница 27: ...nce radiation Class B residential area at nom inal load EN 61000 3 2 Part 3 2 Limits Limits for harmonic current emissions equipment input current 16 A per phase Upper harmonic in put currents Class A...

Страница 28: ...ues Recording and displaying time series of measured values For details see section Display Section Measurement Recording Configurable overload behavior For details see section Dialog Settings Configu...

Страница 29: ...on during transport and storage Store the product in suitable packaging preferably the original packaging Only transport the product in suitable containers packaging Make sure the product contacts are...

Страница 30: ...nt surfaces The letters shown in parentheses refer to positions in the View figure in section View Mounting Positions Nominal mounting position see also figure under View Front side facing forwards ma...

Страница 31: ...e on the top edge of the DIN 35 rail 2 Press the product onto the DIN 35 rail A while simultaneously pulling on the latch I on B until it locks into place 3 To ensure secure fastening on the DIN 35 ra...

Страница 32: ...ca bles see section 8 Technical Data 18 Check the appropriate operating voltage before connecting the equipment see section Type label 7 2 Connect Conductor to CAGE CLAMP CAGE CLAMP Connectors are des...

Страница 33: ...o CAGE CLAMP 1 To open the CAGE CLAMP insert the operating tool into the opening above the connection Once you hear a click the CAGE CLAMP is open 2 Insert the conductor into the corresponding connect...

Страница 34: ...output voltage Press once The output voltage increases in steps Press and hold The output voltage increases con tinuously Press once The output voltage is reduced in steps Press and hold The output vo...

Страница 35: ...Trip ping Current of Electronic Cir cuit Breaker Exceeded 100 Flashing 2 Hz Flashing 2 Hz Flashing 2 Hz 75 Off Flashing 2 Hz Signaling of regular utilization 50 Off Off 25 Off Off DC OK Flashing 2 Hz...

Страница 36: ...Components Requirements Operating system Windows 10 64 bit Memory 8 GB Free hard disk space 250 MB Processor 1 GHz or higher 64 bit x64 Screen resolution 1920 1080 pixels 10 1 2 Install WAGO Interface...

Страница 37: ...ct to a computer via a WAGO USB Communication Cable 10 2 First Steps The following steps are based on the WAGO Interface Configuration software G2 Ver sion 01 00 06 18 and Firmware Version 01 05 xx If...

Страница 38: ...nication Selects the connection between the product and software Language Selects the display language for the software Help Opens the help for the software About Displays information about the softwa...

Страница 39: ...ly selected or automatically detected by the software see the following steps The settings you have to make on this tab depend on whether you are configuring your product offline or online Offline Con...

Страница 40: ...the Graphical User Interface Overview Pos Section Description 1 Menu Bar The menu bar contains general software settings options You can find more information in section Menu Bar 2 Main Menu The main...

Страница 41: ...s and measured values which can be stored as a CSV file Simulation Opens the Simulation dialog The dialog is described in section 8 Dialog Simulation 51 Update Performs a firmware update on the produc...

Страница 42: ...ttons Button Description Import Imports previously saved settings e g when a product is replaced or config uration is performed offline Export Saves the new settings externally The saved settings can...

Страница 43: ...mode a smooth char acteristic curve ensures better current sharing for par allel operation of power supplies Enable switching the DC out put on and off via cyclic process data If this checkbox is sel...

Страница 44: ...c Circuit Breaker overload behavior Latching after thermal over load If this checkbox is selected the Latching Shutdown on Thermal Overload overload behavior is enabled After an overtemperature event...

Страница 45: ...by high low transition If this checkbox is selected the digital input is acti vated in the event of an edge change from 1 to 0 Digital output DC O K 1 If this checkbox is selected the digital output i...

Страница 46: ...g thresholds Overload limit active If this checkbox is selected a warning is triggered if the overload warning threshold is exceeded Warning threshold Here you can enter the value for current unit mA...

Страница 47: ...witched off 1 If this checkbox is selected the DC output remains switched off in the event of connection to the grid Switch on delay active If this checkbox is selected an additional switch on de lay...

Страница 48: ...con nected product with the system time of the PC Customer informa tion Location name Here you can enter additional information on the prod uct used All the input fields can be freely edited You can e...

Страница 49: ...e If this checkbox is selected no parameters can be writ ten to the product Write and read protection ac tive If this checkbox is selected no parameters can be writ ten to the product or read from the...

Страница 50: ...ormation about the Modbus RTU Communication Module is available in the re spective Product Manual and in section 8 Accessories Communication 70 Figure 30 Dialog Settings Modbus Table 56 Dialog Setting...

Страница 51: ...operating states warnings and errors All operating states warnings and errors can be displayed visually Identify the optimal setting options Optimal setting options for a specific load behavior can b...

Страница 52: ...d in the Selection of the signal source operation panel Import load curve view This view appears if the Import load curve setting has been enabled in the Se lection of the signal source operation pane...

Страница 53: ...oints can thus be examined more closely Process Input Data Operation Panel Shows operating states warnings and errors General information on operating states warnings and errors is explained in the Se...

Страница 54: ...ee measured values The representation in the Display section is described in section Display Sec tion Measurement Recording Last Error and Warning Mes sages Shows the last accumulated error messages a...

Страница 55: ...s Section Indicator Description Output Voltage This indicates the current output voltage unit V Current This indicates the current output current unit A Power This indicates the current output power u...

Страница 56: ...ature The displayed value is the sum over the previous operating time unit h The hours themselves are recorded and added up over the entire product life cycle Overheating device switched off This show...

Страница 57: ...Section Measurement Recording Pos Setting Description 1 Chart Clock Here you can specify whether a specific number of val ues chart or measured values over a specific time period clock should be reco...

Страница 58: ...Here you can enter the time when recording should start setting at pos 1 clock End time Here you can enter the time when recording should end setting at pos 1 clock Sample rate Here you can enter the...

Страница 59: ...ection Description No Consecutive number of the accumulated warning and error message Date Date of the accumulated warning and error message Time Time of the accumulated warning and error message Warn...

Страница 60: ...e connect product Table 62 Display Section Information Indicator Description Order number This shows the order number of the product Description This shows the manufacturer s name for the product SW V...

Страница 61: ...ed in the Dialog Set tings dialog in the System section of the WAGO Interface Configuration software The maximum number of products that can be operated in parallel on one circuit is given by the sum...

Страница 62: ...Derating Location Dependent Temperature Value Derating TU 60 C 17 5 1000 m 60 C 2000 m or higher 0 0 5 1 1 5 2 2 5 0 1000 2000 3000 4000 5000 IOUT A Altitude m Tamb 40 C Tamb 50 C Tamb 60 C Figure 38...

Страница 63: ...ce Configuration software 11 5 Short Circuit and Overload Behavior The product s output is electronically protected against overload and short circuits The following values apply to the description be...

Страница 64: ...man ual intervention is necessary The following options are available for this Communication interface Buttons Digital input t 110 100 20s IOUT IN Figure 40 Constant Current with Latching Shutdown Mod...

Страница 65: ...on Thermal Overload Mode In this mode the output voltage is switched off in the event of excessive internal device temperature A corresponding High Device Temperature warning can for example be trans...

Страница 66: ...aused by a short circuit or a large overload in the secondary circuit for example In some cases the current pulse can trip an overcurrent protection device that is present in the connected circuit suc...

Страница 67: ...east every two years The product requires no special maintenance however it must be protected as per the protection class against dust accumulation moisture radiation and aggressive chemi cals Permitt...

Страница 68: ...benefits health protects the environ ment from harmful substances in electrical and electronic equipment and enables sus tainable and efficient use of resources Observe national and local regulations...

Страница 69: ...lustrate examples of how a WAGO Power Supply Pro 2 can be connected as a consumer in three different grounding systems TN TT and IT 13 1 1 AC Operation L N PE Load Source AC 1 phase AC DC Figure 45 AC...

Страница 70: ...89 9015 Attachable Modbus TCP Communication Mod ule for WAGO Power Supply Pro 2 Modbus TCP Communication Module 2789 9052 Attachable EtherNet IP Communication Mod ule for WAGO Power Supply Pro 2 Ether...

Страница 71: ...nd Manufacturers Group e V CODESYS is a registered trademark of CODESYS Development GmbH DALI is a registered trademark of the Digital Illumination Interface Alliance DiiA EtherCAT is a registered tra...

Страница 72: ...l Data Inrush Current 19 Table 17 Technical Data Mains Failure Buffering Time 19 Table 18 Technical Data Input Connection 19 Table 19 Technical Data Output 19 Table 20 Technical Data Output Connection...

Страница 73: ...aphical User Interface Overview 40 Table 50 Device Tab 41 Table 51 Dialog Settings Buttons 42 Table 52 Dialog Settings DC Output 43 Table 53 Dialog Settings Signalization 45 Table 54 Dialog Settings S...

Страница 74: ...ing 31 Figure 17 Connect Conductor to CAGE CLAMP 33 Figure 18 Software Start 37 Figure 19 Start View 37 Figure 20 Start View Tabs 37 Figure 21 Backstage Tab 38 Figure 22 Device Tab Selection Menu Item...

Страница 75: ...62 Figure 39 Constant Current Mode 63 Figure 40 Constant Current with Latching Shutdown Mode 64 Figure 41 Hiccup Mode 64 Figure 42 Electronic Circuit Breaker Mode 65 Figure 43 Power Boost Mode in Comb...

Страница 76: ...gs videos and other WAGO media are subject to copyright Distri bution or modification of the contents of these pages and videos is prohibited Furthermore the content may neither be copied nor made ava...

Отзывы: