OPERATING INSTRUCTIONS, Issue SW1201/ 2.01/ HW2.4

Wagner & Co

Solar Controller SUNGO S

Wagner & Co

The benefits at a glance

Large illuminated display to indicate temperature, bal-
ance values and system status with clearly visible sym-
bols for easy readability.

Easy and safe operation via four buttons for vertical and
horizontal scrolling through the menus.

Extensive diagnostics for monitoring system functions,
eg. sensor cutoff and monitoring of temperature differ-
ence “

T too high”

Integrated security functions such as collector cooling,
tank cooling, system protection and vacuum tube col-
lector function.

Solar charging of 1 tank systems

Current/reset values

3 temperature inputs Pt1000

1 output, speed-controlled

Contents

1.

Technical Description . . . . . . . . . . . . . . . . . . 2

2.

General Safety Guidelines . . . . . . . . . . . . . . . 4

2.1 Installer’s Qualifications . . . . . . . . . . . . . . . . . 4
2.2 Operating Requirements . . . . . . . . . . . . . . . . 4
2.3 Installation and Operating Information . . . . . . . . 4
3.

Installation . . . . . . . . . . . . . . . . . . . . . . . . 4

3.1 Installation of the Case. . . . . . . . . . . . . . . . . . 4
3.2 Connecting Wires . . . . . . . . . . . . . . . . . . . . 5
4.

Operation . . . . . . . . . . . . . . . . . . . . . . . . . 6

4.1 Display and Buttons . . . . . . . . . . . . . . . . . . . 6
4.2 Information Menu . . . . . . . . . . . . . . . . . . . 8
4.3 Settings Menu. . . . . . . . . . . . . . . . . . . . . . 8
4.4 Manual Operation Menu. . . . . . . . . . . . . . . . 9
4.5 Special Functions Menu . . . . . . . . . . . . . . . . 9
4.6 Service – System Messages . . . . . . . . . . . . . . 10
4.7 Service – Sensor Control . . . . . . . . . . . . . . . . 10
5.

Application Examples . . . . . . . . . . . . . . . . . 11

5.1 Standard Single-Tank System . . . . . . . . . . . . . 11
5.2 SECUSOL System . . . . . . . . . . . . . . . . . . . . 12

Figure 1 Solar Controller SUNGO S.

Solar Thermal / Solar Circuit

EN-SUNGO-S-BA-0804-1122P200

1

Содержание SUNGO S

Страница 1: ...otection and vacuum tube col lector function Solar charging of 1 tank systems Current reset values 3 temperature inputs Pt1000 1 output speed controlled Contents 1 TechnicalDescription 2 2 GeneralSafety Guidelines 4 2 1 Installer s Qualifications 4 2 2 OperatingRequirements 4 2 3 InstallationandOperatingInformation 4 3 Installation 4 3 1 Installationof theCase 4 3 2 ConnectingWires 5 4 Operation 6...

Страница 2: ...omatic operation in the information menu Manual Lag Function In order to check the temperature values in the information menu even when the output channels are set manually a time lag has to be selected in the manual lag function of the manual operation menu After exiting the manual opera tion menu this time span passes once and then is set back to zero In this mode a blinking symbol for the manua...

Страница 3: ...f 2 diodes which can be switched anti parallel antiparallel thyristors The thyristors switch through the positive or negative sine half wave as long as a switch on difference exists The triac switch switches off when the temperature falls below the switch off difference System Protection In order to protect system components like solar circulation pump 2 3 way valves etc that are installed in the ...

Страница 4: ...stcheckwiththeserviceof Wagner Co The use of the control for non specified operation re sults in a lapse of the guarantee 2 3 Guidelines for Installation and Operation Because Triacs carry 230V current at the case the mains must be disconnected while any installation and wiring work is carried out The mains must be connected to the control via an exter nal ON OFFswitch outside the solar circulatio...

Страница 5: ...onnection Mains power is connected from outside the connector via an ON OFF switch If the unit is connected with a plug to a socket the switch can be omitted The unit is designed to work with 230V AC 50Hz Please check that your pump has compatible specifications All earth wires are connected to the PE connectors The neutral terminals N are connected electrically Switch output A1 is a 230 Vnormally...

Страница 6: ...enu Information menu Temperature difference Number display for temp or sensor errors Collector temperature Reset symbol Tank temperature lower half Pump ON Pump OFF Output A1 Figure 3 Connections S a f e t y f u s e T1 collector sensor T2 tank sensor lower half T3 tank sensor upper half Mains PE Solar circulation pump PE Mains phase L Mains neutral N Solar circulation pump phase L1 Solar circulati...

Страница 7: ... solar Switch off difference T1 T2 solar Minimum temperature source Set point temperature difference speed control solar Solar circulation pump Maximum speed solar circulation pump SECUSOL System filling time SECUSOL dT max __K dT min __K __ C T max __ C T min T start __ d max __ d min __ __K dT Save value Activate save function Decrease value Increase value Ý Ý Ý Activate value Ý ...

Страница 8: ...erence between collector and tank is higher than switch on difference solar circulation pump on 1 Sensor T3 tank upper half is simply a measuring sensor therefore it is not monitored by the sensor control 4 3 Settings Menu Settings menu Menu item Description Range Base value Temperature limitation tank lower half 15 90 C 85 C Switch on difference between collector and tank 3 40 K 10 K Switch off d...

Страница 9: ... 0 3 SECUSOL system see SECUSOL instructions for further info 1 or 3 1 1 System Protection Off 0 On 1 Activation of system protection Cannot be activated with SECUSOL 0 or 1 1 2 System protection start temperature 115 200 C 135 C 3 Collector Cooling Off 0 On 1 Activation of collector cooling Cannot be activated with SECUSOL 0 or 1 1 4 Collector cooling start temperature 100 150 C 110 C 5 Tank Cool...

Страница 10: ...he line or the sensor input on the controller dT too high A fixed value of 20 K is added to the temperature difference between collector T1 and tank sensor T2 The message is displayed if after 30 minutes the total temperature difference has not been reduced Check pump pump connections wiring Check system for air and vent if required Check sensors sensor lines and change sensor if required 4 7 Serv...

Страница 11: ...GO S P3 P2 Ta A1 T2 T3 T1 CIRCO T2 ECOplus Ttw T3 P1 T1 BWM Hot water Cold water Oil or gas boiler Heating circuit Collector field T1 Collector sensor T2 Tank sensor lower half T3 Tank sensor upper half P1 Solar circulation pump P2 Heating circuit pump P3 Tank charging pump Ttw Hot water sensor heating control BWM Thermostatic mixing valve ...

Страница 12: ...boiler T1 Collector sensor T2 Tank sensor lower half T3 Tank 1 sensor upper half optional P1 Solar circulation pump P2 Heating circuit pump P3 Tank charging pump Ttw Hot water sensor heating control BWM Thermostatic mixing valve Subject to modifications errors excepted Wagner Co 2008 www wagner solar com 12 WAGNER CO Zimmermannstraße 12 D 35091 Cölbe Marburg 49 6421 80 07 0 Fax 80 07 22 ...

Отзывы: