Service tasks
9
Service tasks
9.1
Leak test
Check the AirCon Service Center once a year for leaks in accordance with
the applicable legal requirements. Use an electronic leak detector for this
purpose.
9.2
Calibrating the oil scales
(for ASC 2300 G/ASC 3300 G only)
I
1. In the basic menu, use the cursor keys
or
to select
“Other
selections”
:
2. Press
ENTER
to confirm.
3. Use the cursor keys
or
to select
“Reset scales”
:
✓
You are then prompted to remove the containers from the scale:
NOTE
In order for the oil quantities and the UV additive to be measured
correctly, the zero point of the scales must be checked regularly and
reset if necessary.
Resetting is necessary:
If the quantity in a container deviates by more than 10 ml from the
target value
If the AirCon Service Center has been shaken, for example during
transport on bumpy roads
Every four to six weeks
Short selection
Free selection
Other selections
ENTER-OK
Int. vessel filling
Flushing
Reset scales.
Service.
Remove the 3 Oil/UV
glasses from scales.
ENTER-OK STOP-EXIT