Operation
G 100 / G 120
50
wc_tx001687gb.fm
4.15
Operation
Switch
positions
Leave the engine start switch
(f)
in the START/RUN position while the generator is
operating.
If the generator was started using a remote switch, leave the engine start switch in
the REMOTE START position.
Let the generator run for a few minutes to warm the engine before closing the main
circuit breaker.
While the generator is running, check for excessive vibration, oil leaks, or coolant
leaks.
Generator
Monitoring
Generator information is displayed on the top line of the LCD panel and is scrolled
continuously while the generator is operating, to show the voltage, amperage and
frequency of each phase.
Volts “V”
- Displays the AC output voltage being produced by the generator.
Phase “Ø”
- Indicates which leg is currently being displayed. In three-phase mode,
the display will read P1, P2, or P3. In single-phase mode, the display will read L1,
L3, or LL.
Amps “A”
- Displays the AC output amperage produced by the generator. If the
generator is operating at no-load, output amperage will display a 0.
f
A
Ø
HZ
V
R
B
a
s
le
r
DIAGNOSTICS
DIAGNOSEN
DIAGNOSTICOS
DIAGNOSTICS
AUS
AUS
APAGADO
APAGADO
ARRET
ARRET
OFF
OFF
REMOTE START
REMOTE START
FERNSTART
FERNSTART
ARRANQUE REMOTO
ARRANQUE REMOTO
DEMARRAGE A
DEMARRAGE A
DISTANCE
DISTANCE
START / LAUFEN
START / LAUFEN
ARRANQUE / MARCHA
ARRANQUE / MARCHA
DEMARRER / MARCHE
DEMARRER / MARCHE
START / RUN
START / RUN
CAUTION
Possibility of unexpected equipment start-up.
f
Disconnect all attached electrical devices before starting the machine.
f
Before closing breakers, make sure that any electrical devices attached down-
stream from the generator will not start up unexpectedly.
f
Before placing the engine start switch in the REMOTE START position, verify
that the contacts on any remote switch linked to the generator set are
open
.
This will prevent the generator from immediately starting when the engine start
switch is moved to the REMOTE START position.
Содержание G 100
Страница 1: ...5000185616 04 0911 5 0 0 0 1 8 5 6 1 6 Operator s Manual Mobile Generator G 100 G 120 EN...
Страница 5: ...G 100 G 120 Foreword wc_tx000994gb fm 5...
Страница 6: ...Foreword G 100 G 120 6 wc_tx000994gb fm...
Страница 10: ...10 wc_bo5000185616_04TOC fm Table of Contents G 100 G 120...
Страница 33: ...G 100 G 120 Lifting and Transporting wc_tx001191gb fm 33 Notes...
Страница 90: ...Technical Data G 100 G 120 90 wc_td000298gb fm Notes...
Страница 91: ...G 100 G 120 Schematics wc_tx000998gb fm 91 10 Schematics This page is intentionally left blank...
Страница 96: ......
Страница 97: ......