8.10 Frequency limit
If the speed value exceeds the frequency limit 2107h a warning flag is set (no EMCY).
The valid area is 1 to 65535 representing the maximum allowed rotation speed (e.g.
2520 rpm = 42 rotations per second = 002Ah as frequency limit).
8.11 CAM-configuration
This section gives an example how to configure the cam-channel:
That means for single cams:
CAM
Angular area
lower CAM-
limit
upper CAM-
limit
Hysteresis
1
0°..180°
0
2048
0
2
180°..360°
2049
4095
0
3
0°..60°
0
682
0
Table 8.67: Example CAM-configuration
The configuration must be done in Pre-Operational state.
To enable the individual cams the CAM-enable-register (object 6301h-01h) is used.
For example the setting 00000111b = 07h enables the first three cams.
600h+ID 5
2Fh
01h
63h
01h
07h
00h
00h
00h
CAN-ID
DLC Command Object
L
Object
H
Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.68: Enable first three cams
CAM1 0°=>180°
CAM2 180°=>360°
CAM3 0°=> 60°