Technical Manual
WDGA with CANopen-Interface
8 - Setting-up the encoder
© Wachendorff Automation GmbH & Co. KG
64
Rev.1.24
The singleturn resolution is editable in object 6001h:
600h+ID 8
23h
01h
60h
00h
00h
10h
00h
00h
CAN-ID
DLC Command Object
L
Object
H
Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.63: Change of singleturn-resolution by SDO
00 00 10 00h represent the designated singleturn resolution. The encoder responds
with a SDO acknowledge.
The total measuring range can be changed similarly by object 6002h. In the example
a 29 bit total measuring range is selected. With a 12 bit singleturn resolution 17 bit
rotations are counted before returning to zero:
600h+ID 8
23h
02h
60h
00h
00h
00h
00h
20h
CAN-ID
DLC Command Object
L
Object
H
Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.64: Change of total measuring range by SDO
20 00 00 00h is the designated total measuring range.
Singleturn resolution and total measuring range do not have to match the bit grid. Every
value between 1 and the maximum is valid. The total measuring range cannot be less
than the singleturn resolution. The result of an invalid setting will be an abort code.
From revision number (software version) 1.12, it is no longer
possible to scale object 6004 to 32 bits. Only devices, ordered
as a 32-bit device (default resolution = 32-bit) provide full 32-
bit resolution. Object 6002 has a "0". For all other variants, only
a scaling to 2
32 -1
is possible.
8.7 Position preset
With object 6003h the encoder position can be shifted to a preset value. E.g. you can
set the zero position of your application without time-consuming mechanical alignment.
Just mount the encoder and set the preset object 6003h to the designated position
value (p1-p4):
600h+ID 8
23h
03h
60h
00h
p1
p2
p3
p4
CAN-ID
DLC Command Object
L
Object
H
Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.65: Set position preset
To set the zero position: p1, p2, p3, p4 = 00h, 00h, 00h, 00h