118
UR3274U - User manual
61
Lo.L.r.
Lower Limit Retransmission
lower limit retransmission range.
-999 - 9999
[digit
8
], (degrees for temperature sensors) >
Default
: 0.
62
up.L.r.
Upper Limit Retransmission
upper limit retransmission range.
-999 – 9999
[digit
9
], (degrees for temperature sensors) >
Default
: 0.
63
tmr.f.
Timer Function
enable 1 or 2 Timers which may be set from user menu
and which can be related to alarms.
dis.
Disable >
Default
s.tm.s.
Single Timer Seconds
d.tm.s.
Double Timer Seconds
d.s.t.s.
Double Sequential Timer Seconds
d.t.L.s.
Double Timer Loop Seconds
s.tm.m.
Single Timer Minutes
d.tm.m.
Double Timer Minutes
d.s.t.m.
Double Sequential Timer Minutes
d.t.L.m.
Double Timer Loop Minutes
64
Fa.Gr.
Falling Gradient
cooling gradient for pre-programmed cycle
0
desabled (uncontrolled cooling) >
Default
: 0.
1-9999
degrees/hour, with display of tenths
8
The display of decimal point depends on the setting of parameter
sen.
and the parameter
d.p.
9
If parameter 61
Lo.L.r.
and 62
up.L.r.
have the same value, retransmit-
ted value is not rescaled.