6 Appendix
6.2 Failure monitoring
Following possible error sources are monitored continuously when SENS = ON/AUTO:
Source
Fault
Characteristic
Command signal PIN 10
4... 20 mA
Out of range or broken wire
The output will be switched off.
Command signal PIN 6
4... 20 mA
Out of range or broken wire
The output will be switched off.
Feedback signal PIN 13
4… 20 mA
Out of range or broken wire
The output will be switched off.
Feedback signal PIN 14
4… 20 mA
Out of range or broken wire
The output will be switched off.
EEPROM
(when switching on)
Data error
The output is deactivated.
The module can only be acti-
vated by saving the parameters
again!
CAUTION:
Take care of the EOUT command. Changes will influence the behavior.