Page 49 of 53
POS-123-P-PFN
8 Profinet-Driver Blocks for Simatic-Controllers
8.1 Integration of the Block into the PLC program
For use within the
„TIA Portal“ software we provide two driver blocks that enable a convenient access out of
the application program:
a)
The source WEST_POS_123_P_PFN.scl for controllers of the S7-1200 and -1500 series
b)
The source WEST_POS_123_P_PFN_TIA_KLASSIK.scl for controllers of the S7-300 and -400 series
Below their integration in the TIA project and the interconnections are explained.
c)
Import the GSDML-file
d)
Project the connection between PLC and controller card via Profinet:
1.) In the device a modul
e „IN/OUT 32 bytes“ has been assembled by the system:
The addresses will be assigned automatically. Important for the link of the program block is the hardware iden-
tifier, which is also assigned automatically. This only applies if a S7-1200 / -1500 controller is used.
To determine the identifier right-
click in the project tree on the device, choose “properties” and take over the
number which is displayed in the tab “System constants”:
If a controller of the S7-300 and -400 series is used, the input and output addresses of the I/O-Module are the
required information for the driver block, see over.
Содержание POS-123-P-PFN
Страница 11: ...Page 11 of 53 POS 123 P PFN 31 03 2021...
Страница 53: ...Page 53 of 53 POS 123 P PFN 31 03 2021 9 Notes...