MULTI GAS LEAK DETECTOR
ME-LOKATOR VL30 – REFRIGERANT GASES
PAGE |
7
LOKATOR VL 30 EN
4.2
LOKATOR VL30 FIRST START
4.2.1
VERIFICATIONS BEFORE START-UP
• Check whether the probe and the connection cable to the cabinet are mechanically intact. The connecting cable must not be
wrinkled, crushed, deformed or tear.
• Connecting or disconnecting the probe or the cable to the LOKATOR VL30 Cabinet must only be done when the LOKATOR
VL30 is not operating.
4.2.2
START-UP
• Toggle the ON / OFF power switch on the back of the cabinet.
The RED LED on the front panel of the cabinet lights up to indicate Mains power.
• Wait 15 seconds and press the push button on the front panel for at least 2 seconds.
• The green LED on the front panel lights up to indicate that the Detector is ON.
4.2.3
STARTING SEQUENCE
The LOKATOR VL30's light ramp and the LCD screen will light on and display successively:
• Indicates the countdown of the heating period: 180 seconds
• Each led of the detection lights ramp cyclically one by one.
• The detector has completed its initialization and
automatically switches to detection mode.
• The GREEN light of the zero is lit and the RED light of the
Probe is off.
• The LOKATOR VL30 is ready for operation !
3
DETECTION screen
1
system initialization
2
Warm-up of the probe