8
-
VCRG-M / WCRG-M PILOT LIGHTING PROCEDURE
1. Turn the main gas shut-off valve and all burner control knobs to the OFF position. Wait 5 minutes to
allow any gas that may have accumulated in the burner compartment to escape.
2. Turn the main gas shut-off valve ON.
3. While viewing through the pilot sight hole, you will have to reach under the front of the unit and through
the pilot cutout to ignite the pilots with an outside ignition source(such as a lit taper, etc.). It may be
necessary to adjust the pilot valve to increase gas to the pilot. See Fig. 7 on page 11.
4. Repeat steps until all pilots are lit
5. To light main burners, turn individual burner valves to the ON position.
5. If after completing steps 1-5 main burners do not light, turn off the main gas shut-off valve and
contact an authorized service contractor.
CUTAWAY VIEW
BURNER CONTROL KNOB
PILOT SIGHT HOLE
PILOT BURNER
7”