background image

VALTRONICS

R59 Zero Adjust

R58 Span Adjust

1

8

TB1

Green Power

Red Level Exceeded

Set Point

Adjust

R47 Coarse Zero
DO NOT Adjust

R33 Sample Rate
DO NOT Adjust

R3

E1

E2

E3

JP1 shown in
FIXED position

Optional LCD

Display

J1

Set

Point
Relay

K1

9 pin "D"
Test Connector
J2

F1

0.5 Amp

Slow-Blow

Fuse

3 position

Fixed Level Detect

Switch S1

7
6
5
4
3
2

1

5

6

9

TB1

Model 6289 Wiring

3463 Double Springs Road • Valley Springs, CA 95252 • (209) 754-0707 • FAX (209) 754-0104

Page 1 

of 3       e-mail:

   

[email protected]

 

  •   Revised: : 

10-May-01 

 © 1994-2001 

VALTRONICS

0-5 V out 

pin 

6

 to 

5

 with DVM

to 4-20 mA input at
controller

 - DO NOT

connect 26 VDC

From 24VAC
transformer

The 

4-20 mA  current loop

 (pins 4 & 5)

 has its own 15

VDC internal power supply so NO External Power is
required in this loop.   Pins 1, 2, 3, are the SET Point
Relay contacts -  see the 6289 specification.

20.0 V min

 / 30 max

12 VA 

power rating

Level Detect Switch
Middle position is 1000
ppm or 2.5 volts. This
does not effect the
calibration of the sensor
just when the relay
energizes and the RED
indicator comes on.
Customers using an
HVAC controller to
monitor the 4-20 mA
output signal may not
use this function at all.
Placing the jumper JP1 in
the variable position E2
to E3 and adjusting
potentiometer R3 fully
clockwise will keep the
RED indicator OFF until
the level goes above 2000
ppm.

See Application Notes
A25 or A40 for info
about gas calibration
and page 2 for 

ZERO

on fresh air.  Gas
calibration kits allow
you to flow certified
gas into the

 

green

plastic cal tube at about
300 ml/min flow rate.
The tube should be
pinched off for normal
operation.

optional ground on pin 8

A minor ZERO adjustment
on fresh air of about 400 ppm
CO

2

 may be necessary after

installation.  Adjust R59
(ZERO) next to the RED
indicator for a 0-5 voltage
output of 1.0 volts for fresh
air.  Try to assure that the air
is fresh inside the duct.  DO
NOT adjust SPAN without
calibration gas.

The COARSE ZERO
adjust may be used to
center the fine zero
adjust R59 but adjust it
slowly.

 There is a 10

second delay

 in the

response.

Application 

Note A51

Model 6289 Wiring & Calibration Adjustments

CAUTION

:  DO NOT connect a Model 6289 to the same

24 VAC transformer that powers an older Model 2088 or
2089

 since they require a floating 24 VAC.  TB1, Pin #8 on

the 6289 is  grounded and this may burn out the 2088 or
2089 power supply.

8
7
6
5
4
3
2
1

24 VAC

TB1

Отзывы: