VSL2.909.031ASY                                                                                           

                         

  V1.04

 

Features 

 

Easy Installation

   

 

Loop power supply 

 

Both side

 isolate control 

 

Designed to comply with EN 54-17 

Description 

VI-6777 Digital Isolate Interface monitors the short circuit fault at the loop detection zone ,It has both side isolate 

function ,if detects the short circuit on loop it will isolate that side to ensure loop communication signal will not be 

affected or interrupt by short-circuit fault. When the short circuit fault is removed, the isolate interface will 

automatically restore loop. 

Technical data 

Operating Voltage: 

18-28V(Modulated-pulse) 

Standby Current: 

1mA 

Isolate holding current 

10mA 

Action condition 

Isolate input/output side short circuit or loop voltage 

7.5V

 

Wiring 

Two-wire

non-polarized

 

Temperature range: 

-10

℃~

50

 

Humidity: 

95%RH, 

40

±

2

℃)

No condensation 

Isolate Indication: 

Active A or Active B 

LED illuminates steadily. 

IP Rating: 

32 

Installation Base 

VB-6618 

Note:

The VI-6777 Isolate interface is working with VSAIL Digital Protocol 

Installation 

 

Dimensions

Showing on Fig.1 

 

 

Fig.1 

 

Mounting: 

Warning:  Please  disconnect the  loop power  in  order  to  avoid control panel  broken by short  circuit when 
mounting Base. 

1.Make sure the mounting direction mark “

” on Base is upwards . 

2.Install the base stable by using two screws,and connect all cables in accordance with wiring details. 

3.Install the Isolate interface body on to base directly. 

4.Isolate interface Mounting showing in Fig.2 

Installation and Operation Manual V1.04

 

VI-6777 Digital Isolate Interface 

Beijing VSAIL Fire Protection Equipment Co. Ltd.

 

Building 32, Huilongsen Technology Park,   
No.99 14th Kechuang Street, BDA, Beijing, PRC 