VZR.2515.001IM
CUBE C-05 tripod turnstile
Installation Manual
32
PANEL UCP 02. TO CONNECT BCP 01 TO THE CONTROLLER, THE
CONTROLLER SHALL HAVE PROGRAMMABLE INPUTS THAT WILL RECEIVE
CIRCUITS FROM THE REMOTE. IN THIS CASE, CONTROLLERS PERCEPT
OPENING AS BUTTON PRESSING BUT NOT AS THE OPENING FROM THE
CONTROL PANEL.
In some cases, turnstile CP should be connected directly to ACS controller,
since the system responds to passing allowed from the control panel (without the
use of controller) as to “hacking”.
To use this diagram for connecting the turnstile, it is necessary to set the
control board to mode number 6 using the BUT button (see Table 1). With this
setting, the turnstile does not respond to the control panel commands and only
transmits their status to the terminals of the ACCES_OUT control board terminal
blocks. Figure 10
– (LEFT, RIGHT, STOP, AP), which are outputs with an open
collector.
The contact assignment is shown in Table 4, Figure 12
– numbering of the
control panel buttons. For this group of contacts, the maximum output current is
not more than 150 mA and permissible voltage is not more than 12 V.