Specifications 

INPUT MODULE SPECIFICATION SUMMARY 

Parameter 

Details 

Min 

Typical 

Max 

Units 

AC Input Voltage 

Nominal range is 100V

RMS

 to 240V

RMS

 

85 

 

264 

V

RMS

 

AC Input Frequency 

Contact factory for 400Hz operation. 

47 

50/60 

63 

Hz 

DC Input Voltage

3

 

Standard (S/SL) 
Medical (M/ML) 

120 
120 

 

370 
300 

V

DC

 

Output Power Rating 

Standard & Medical (S/M) - De-rate linearly from 600Watts at 120V

RMS

 to 450Watts at 85V

RMS 

Low Noise (SL/ML) - De-rate linearly from 450Watts at 120V

RMS

 to 338Watts at 85V

RMS 

 

 

600 
450 

Watts 

Input Current 

Standard & Medical (S/M) - 600Watts output at 120Vrms input 
Low Noise (SL/ML) - 450Watts output at 120Vrms input 

 

 


Amps 

Fusing 

Live line fused (5x20 Fast acting) 

 

 

Amps 

Power Factor 

Typical value for 300 Watts output at 240Vrms input 

 

0.96 

0.99 

 

Size 

133.7 (L) x 77.7 (W) x 41.0 (H). See diagram for tolerance details 

mm 

Weight 

360 + 60 per output module 

Grams 

Notes 
 

1.

 

NEVO+ input modules can only be used with NEVO+ output modules and must not be used for any other purpose. 

2.

 

Only use a power source of the type indicated on the product label. 

3.

 

Not covered by safety approvals. Contact Vox Power. 

 

 

OUTPUT MODULE SPECIFICATION SUMMARY

 

MODEL 

Output Voltage 

Output 

Current 

Rated 

Power 

Peak 

Power 

Load 

Reg. 

Line 
Reg. 

Cross 

Reg. 

Ripple & 

Noise 

FPMH 

(1)

 

Feature 

Set 

(2)

 

Min. 

Nom. 

Max. 

OP1 

1.5V 

5V 

7.5V 

25A 

125W 

187.5W 

±50mV 

±5mV 

±10mV 

50mV

PP

 

0.5 

ABCDEFG 

OP2 

4.5V 

12V 

15V 

15A 

150W 

225W 

±100mV 

±12mV 

±24mV 

120mV

PP

 

0.5 

ABCDEFG 

OP3 

9V 

24V 

30V 

7.5A 

150W 

225W 

±150mV 

±24mV 

±48mV 

240mV

PP

 

0.5 

ABCDEFG 

OP4 

18V 

48V 

58V 

3.75A 

150W 

217.5W 

±300mV 

±48mV 

±96mV 

480mV

PP

 

0.5 

ABCDEFG 

OP5 

3.3V 

12V 

15V 

5A 

2x 75W 

2x 75W 

±50mV 

±12mV 

±24mV 

240mV

PP

 

0.75 

AFG 

OP8 

23.2V 

24V 

24.7V 

3.125A 

2x 75W 

2x 75W 

±100mV 

±24mV 

±48mV 

480mV

PP

 

0.75 

AFG 

OPA2

(3)

 

4.5V 

12V 

15V 

25A 

300W 

375W 

±100mV 

±12mV 

±24mV 

120mV

PP

 

0.5 

ABCDEFGH 

OPA3

(3)

 

9V 

24V 

30V 

15A 

300W 

450W 

±150mV 

±24mV 

±48mV 

240mV

PP

 

0.5 

ABCDEFGH 

Note 1. 

Output module, 30˚C base, 100% load, SR332 issue 2 Method I, Case 3, Ground, Fixed, Controlled 

Note 2. 

 

Note 3. 

A = Remote Sense, B = External Voltage control, C = External constant current control, D = Current output signal, E = Current share, F =Over Voltage protection, 
G = Over temperature protection, H = Dual Slot module 
Can only be used with NEVO+600 chassis with date codes from 2048 onwards.  eg. 2048C080000 can use A2 or A3 module, 2047C089999 cannot use A2 or A3 module. 

 

 
 

 

 

SAFETY SPECIFICATIONS

 

Parameter 

Details 

Max 

Units 

 

Isolation Voltages 

Input to Output (2 MOPP). Do not perform test on assembled unit

(1)

 

4000 

V

AC

 

Input to Chassis (1 MOPP) 

1500 

V

AC

 

Global signals (J2) to Output/Chassis 

250 

V

DC

 

Output to Output/Chassis (Standard modules) 

250 

V

DC

 

Earth Leakage Current 

INDUSTRIAL: Normal condition, 264Vac, 63Hz, 25°C 

1500 

uA 

MEDICAL: Normal condition, 264Vac, 63Hz, 25°C 

300 

uA 

Touch Leakage Current 

Standard modules NC/SFC 

20/200 

uA 

Patient Leakage Current 

Standard modules 264Vac, 63Hz, 25°C NC/SFC

(2)

 

----- 

uA 

Note 1. Testing an assembled unit to 4000V

AC

 may cause damage. Please refer to application note (APN-002) on Vox Power website or contact Vox Power representative. 

Note 2. Not Applicable 

INSTALLATION SPECIFICATIONS

 

Parameter 

Details 

Parameter 

Details 

Equipment class 

Flammability Rating

 

94V-2 

Overvoltage category 

II 

Ingress protection rating

 

IP10 

Material Group 

IIIb (indoor use only) 

ROHS compliance

 

2011/65/EU 

Pollution degree 

Intended usage environment

 

Home Healthcare (M/ML)/ Industrial (S/SL) 

 

 

ENVIRONMENTAL SPECIFICATIONS 

Parameter 

Details 

Non-Operational 

Operational 

Units 

Min 

Max 

Min 

Max 

Air Temperature 

Operational limits subject to appropriate de-ratings 

-40 

+85 

-20 

70

(1)

 

°C 

Humidity 

Relative, non-condensing 

95 

95 

Altitude 

 

-200 

5000 

-200 

5000

(2)

 

Air Pressure 

 

52 

106 

52

(2)

 

106 

kPa 

Noise Level 

Standard Versions (S/M) - Variable.  Measured 1m from fan intake. 

36 

60 

dBA 

 

Low Noise Versions (SL/ML) - Variable.  Measured 1m from fan intake. 

18 

42 

 

Shock 

3000 bumps at 10G (16ms) half sine wave 

Vibration 

1.5G 10 to 200Hz sine wave, 20G for 15min in 3 axes random vibration 

Notes 

1. 

Derate input and all outputs at 2.5%/°C above 50°C. 

2. 

3000m & 68kPa for IEC/UL60601-1. 

Содержание NEVO+600 Series

Страница 1: ... rated by 2 5 C above 50 C ambient up to a maximum ambient temperature of 70 C Input Voltage Standard Medical S M The input module power must be de rated by 4 28W VRMS below120 VRMS 600W 120 VRMS 450W 85 VRMS Low Noise SL ML The input module power must be de rated by 3 21W VRMS below120 VRMS 450W 120 VRMS 338W 85 VRMS Remember to take the appropriate de rating into consideration before specifying ...

Страница 2: ...150mV 24mV 48mV 240mVPP 0 5 ABCDEFGH Note 1 Output module 30 C base 100 load SR332 issue 2 Method I Case 3 Ground Fixed Controlled Note 2 Note 3 A Remote Sense B External Voltage control C External constant current control D Current output signal E Current share F Over Voltage protection G Over temperature protection H Dual Slot module Can only be used with NEVO 600 chassis with date codes from 20...

Страница 3: ...Dimensions and Mounting SCREWS Location Details Penetration Tightening Output Module Mount 2 per module M3 POZI CSK 5mm max length 0 5NM Input module Mount MH1 3 Bottom MH4 5 Side M4 4mm max including chassis 0 5NM Top Cover Mount 5x M3 POZI CSK 1x M2 5 POZI CSK 5mm max length 4mm max length 0 5NM Unless stated otherwise all dimensions are in millimetres and in accordance with DIN2768 1 2 CLASS C ...

Страница 4: ...Tab Size 6 35x0 8mm VARIOUS 2 VARIOUS J5 Output Signals 6 PIN 1 25mm with Friction Lock 28 30AWG MOLEX 2 1510210600 50058800 Notes 1 Terminal and wire current rating must exceed maximum short circuit output current Eg Output 1 25A 1 25 31 25Amps 2 Direct equivalents may be used for any connector parts 3 All cables must be rated 105 C min equivalent to UL1015 4 Pinout is for single output types onl...

Отзывы: