Page 2 of 4
Vox Power Limited | Unit 2, Red Cow Interchange Estate, Ballymount, Dublin 22, D22 Y8H2, Ireland | T +353 1 4591161 |
DOC-MN-001-05, NEVO+600 Series Installation Manual
Specifications
INPUT MODULE SPECIFICATION SUMMARY
Parameter
Details
Min
Typical
Max
Units
AC Input Voltage
Nominal range is 100V
RMS
to 240V
RMS
85
264
V
RMS
AC Input Frequency
Contact factory for 400Hz operation.
47
50/60
63
Hz
DC Input Voltage
3
Standard (S/SL)
Medical (M/ML)
120
120
370
300
V
DC
Output Power Rating
Standard & Medical (S/M) - De-rate linearly from 600Watts at 120V
RMS
to 450Watts at 85V
RMS
Low Noise (SL/ML) - De-rate linearly from 450Watts at 120V
RMS
to 338Watts at 85V
RMS
600
450
Watts
Input Current
Standard & Medical (S/M) - 600Watts output at 120Vrms input
Low Noise (SL/ML) - 450Watts output at 120Vrms input
6
5
Amps
Fusing
Live line fused (5x20 Fast acting)
8
Amps
Power Factor
Typical value for 300 Watts output at 240Vrms input
0.96
0.99
Size
133.7 (L) x 77.7 (W) x 41.0 (H). See diagram for tolerance details
mm
Weight
360 + 60 per output module
Grams
Notes
1.
NEVO+ input modules can only be used with NEVO+ output modules and must not be used for any other purpose.
2.
Only use a power source of the type indicated on the product label.
3.
Not covered by safety approvals. Contact Vox Power.
OUTPUT MODULE SPECIFICATION SUMMARY
MODEL
Output Voltage
Output
Current
Rated
Power
Peak
Power
Load
Reg.
Line
Reg.
Cross
Reg.
Ripple &
Noise
FPMH
(1)
Feature
Set
(2)
Min.
Nom.
Max.
OP1
1.5V
5V
7.5V
25A
125W
187.5W
±50mV
±5mV
±10mV
50mV
PP
0.5
ABCDEFG
OP2
4.5V
12V
15V
15A
150W
225W
±100mV
±12mV
±24mV
120mV
PP
0.5
ABCDEFG
OP3
9V
24V
30V
7.5A
150W
225W
±150mV
±24mV
±48mV
240mV
PP
0.5
ABCDEFG
OP4
18V
48V
58V
3.75A
150W
217.5W
±300mV
±48mV
±96mV
480mV
PP
0.5
ABCDEFG
OP5
3.3V
12V
15V
5A
2x 75W
2x 75W
±50mV
±12mV
±24mV
240mV
PP
0.75
AFG
OP8
23.2V
24V
24.7V
3.125A
2x 75W
2x 75W
±100mV
±24mV
±48mV
480mV
PP
0.75
AFG
OPA2
(3)
4.5V
12V
15V
25A
300W
375W
±100mV
±12mV
±24mV
120mV
PP
0.5
ABCDEFGH
OPA3
(3)
9V
24V
30V
15A
300W
450W
±150mV
±24mV
±48mV
240mV
PP
0.5
ABCDEFGH
Note 1.
Output module, 30˚C base, 100% load, SR332 issue 2 Method I, Case 3, Ground, Fixed, Controlled
Note 2.
Note 3.
A = Remote Sense, B = External Voltage control, C = External constant current control, D = Current output signal, E = Current share, F =Over Voltage protection,
G = Over temperature protection, H = Dual Slot module
Can only be used with NEVO+600 chassis with date codes from 2048 onwards. eg. 2048C080000 can use A2 or A3 module, 2047C089999 cannot use A2 or A3 module.
SAFETY SPECIFICATIONS
Parameter
Details
Max
Units
Isolation Voltages
Input to Output (2 MOPP). Do not perform test on assembled unit
(1)
4000
V
AC
Input to Chassis (1 MOPP)
1500
V
AC
Global signals (J2) to Output/Chassis
250
V
DC
Output to Output/Chassis (Standard modules)
250
V
DC
Earth Leakage Current
INDUSTRIAL: Normal condition, 264Vac, 63Hz, 25°C
1500
uA
MEDICAL: Normal condition, 264Vac, 63Hz, 25°C
300
uA
Touch Leakage Current
Standard modules NC/SFC
20/200
uA
Patient Leakage Current
Standard modules 264Vac, 63Hz, 25°C NC/SFC
(2)
-----
uA
Note 1. Testing an assembled unit to 4000V
AC
may cause damage. Please refer to application note (APN-002) on Vox Power website or contact Vox Power representative.
Note 2. Not Applicable
INSTALLATION SPECIFICATIONS
Parameter
Details
Parameter
Details
Equipment class
I
Flammability Rating
94V-2
Overvoltage category
II
Ingress protection rating
IP10
Material Group
IIIb (indoor use only)
ROHS compliance
2011/65/EU
Pollution degree
2
Intended usage environment
Home Healthcare (M/ML)/ Industrial (S/SL)
ENVIRONMENTAL SPECIFICATIONS
Parameter
Details
Non-Operational
Operational
Units
Min
Max
Min
Max
Air Temperature
Operational limits subject to appropriate de-ratings
-40
+85
-20
70
(1)
°C
Humidity
Relative, non-condensing
5
95
5
95
%
Altitude
-200
5000
-200
5000
(2)
m
Air Pressure
52
106
52
(2)
106
kPa
Noise Level
Standard Versions (S/M) - Variable. Measured 1m from fan intake.
-
-
36
60
dBA
Low Noise Versions (SL/ML) - Variable. Measured 1m from fan intake.
-
-
18
42
Shock
3000 bumps at 10G (16ms) half sine wave
Vibration
1.5G 10 to 200Hz sine wave, 20G for 15min in 3 axes random vibration
Notes
1.
Derate input and all outputs at 2.5%/°C above 50°C.
2.
3000m & 68kPa for IEC/UL60601-1.