Name [ID]
Description
Def.
BIN3 Filter
[180]
Time constant of the binary signal filter.
10 ms
0
ms
÷
30000 ms
Binary input is switched on when the voltage level defined by parameter BIN HW Type [172]
(page 75) is present longer than the value of this parameter and is switched off when the voltage
is not present longer than the value of this parameter.
BIN3 Logic
[718]
Determines the binary input evaluation mode. Binary input hardware settings need to
be taken into account.
Direct
Look choises of parameter's BIN1 Logic [716] (page 75)
BIN4 Filter
[181]
Time constant of the binary signal filter.
10 ms
0
ms
÷
30000 ms
Binary input is switched on when the voltage level defined by parameter BIN HW Type [172]
(page 75) is present longer than the value of this parameter and is switched off when the voltage
is not present longer than the value of this parameter.
BIN4 Logic
[719]
Determines the binary input evaluation mode. Binary input hardware settings need to
be taken into account.
Direct
Look choises of parameter's BIN1 Logic [716] (page 75)
BIN5 Filter
[182]
Time constant of the binary signal filter.
10 ms
0
ms
÷
30000 ms
Binary input is switched on when the voltage level defined by parameter BIN HW Type [172]
(page 75) is present longer than the value of this parameter and is switched off when the voltage
is not present longer than the value of this parameter.
BIN5 Logic
[720]
Determines the binary input evaluation mode. Binary input hardware settings need to
be taken into account.
Direct
Look choises of parameter's BIN1 Logic [716] (page 75)
BIN6 Filter
[183]
Time constant of the binary signal filter.
10 ms
0
ms
÷
30000 ms
Binary input is switched on when the voltage level defined by parameter BIN HW Type [172]
(page 75) is present longer than the value of this parameter and is switched off when the voltage
is not present longer than the value of this parameter.
BIN6 Logic
[721]
Determines the binary input evaluation mode. Binary input hardware settings need to
be taken into account.
Direct
Look choises of parameter's BIN1 Logic [716] (page 75)
7.6.2 ANALOG INPUTS
Group of parameters number [144]
Settings of the analog inputs, which are used for input, setting or continuous measurement of signals like
frequency setpoint, pressure, fluid level etc.
AIN1
Group of parameters number [147]
First analog input.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG INPUTS \ AIN1
Name
[ID]
Description
Def.
AIN1
Type
[153]
Analog input type.
0-10V
0-10V
Analog input level corresponds with the voltage, which is measured between the terminals X1:11
and X1:12 in the 0 to 10V
(~0 až 100%) DC range.
2-10V
Analog input level corresponds with the voltage, which is measured between the terminals X1:11
and X1:12 in the 2 to 10V(~0 až 100%) DC range. If this voltage drops under the 2V limit, the
frequency converter generates the fault " E25-Interrupted AIN1 (page 33)". Fault evaluation can be
turned off using AIN Fault [837] (page 108).
0-20mA
Analog input level corresponds with the current, which is measured between the terminals X1:11
and X1:12 in the 0 to 20mA(~0 až 100%) range.
4-20mA Analog input level corresponds with the current, which is measured between the terminals X1:11