UNIFREM v.3.41x
10 May 2017
Page 26 from 180
Name [ID]
Description
Dim.
□
Switching
On
Inhibited
Reset or Quick stop are active, or an initialization or fault are present.
□ Warning Present
Warning or functional message occurred in the converter.
□ Speed Error within
tolerance
When active, the setpoint frequency is achieved.
□ Control Requested
Inactive - converter does not accept Control Word over communication. Acitve -
converter is controlled by Control Word received over communication.
□ F or n Reached
When active, the setpoint frequency is achieved.
□ Run
Converter generates voltage on the outputs.
□ Set b0
Bit 0 of active set binary combination.
□ Set b1
Bit 1 of active set binary combination.
□ LB3
Status of logical block 3.
□ LB4
Status of logical block 4.
CW_PB [805]
Command word sent by the Profibus master. For a more detailed description,
see the documentation for Profibus Extension Module.
□
ON
Converter is ready to accept the START command.
□ No OFF 2
Inactive - Reset is active, Active - normal converter operation.
□ No OFF 3
Inactive - Quick stop is active, active - normal converter operation.
□ Enable Operation
Start. Converter starts generating voltage on its output terminals.
□
Enable
Ramp
Generator
Inactive - ramp input is set to zero, active - normal operation of the ramp input block.
□ Unfreeze Ramp
Inactive - ramp output is frozen, active - ramp is operating normally.
□ Enable Setpoint
Inactive - ramp input is set to zero, active - normal operation of the ramp input block.
□ Fault Acknowledge
Fault acknowledgement (only transition inactive-active). Fault acknowledgement has
to be allowed in Fault acknowledgement source [165] (page 109).
□ Bit 8
Unused
□ Bit 9
Unused
□ Control by
PLC
Inactive - converter does not accept Control Word. Active - converter is controlled by
Control Word.
□ Bit 11
Unused
□ Bit 12
Unused
□ Bit 13
Unused
□ Bit 14
Unused
□ Bit 15
Unused
PB-MASTER
Error
[819]
Number of communication errors between the Profibus module and the Profibus
master.
hex
PB-INV Error [818]
Number of communication errors between the converter and the Profibus
module.
hex
4.7.3 RS LINKS
Group of parameters number [228]
Serial lines diagnostics.
MENU \ DIAGNOSTICS \ COMMUNICATION \ RS LINKS
Name [ID]
Description
Dim.
FRAME_ERR_USB [232]
USB wrongly received data count. (wrong parity, wrong stop bit,...)
FRAME_ERR_RS485 [229]
RS 485 wrongly received data count. (wrong parity, wrong stop bit,
...)
FRAME_ERR_EXT_MODUL
[233]
RS external module wrongly received data count. (wrong parity,
wrong stop bit,...)
4.8 SW and HW version
Group of parameters number [762]
Information about the converter and its components (Mostly static information).