![Vonsch Quatrofrem Series Скачать руководство пользователя страница 149](http://html1.mh-extra.com/html/vonsch/quatrofrem-series/quatrofrem-series_configuration-and-diagnostics_1049784149.webp)
UNIFREM v.3.41x
10 May 2017
Page 149 from 180
Optimization
–
principle of the operation by maximizing the power using frequency
Example:
Optimization operation on the drive
(thick line - OPT. Output, thin line - Power drain). In this case, the Start Direction (ID = 426) is set
to "From maximum".
A
–
Optimization starting point found by
scanning. It will be configured accurately later
during fine tuning.
B
–
Technological conditions change
–
optimization output settling and finding the new
optimum point.
8.11 External thermal protection (ETP)
If there is a temperature sensor or system of multiple sensors of the same type on the device, of
which the frequency converter is a part, it is possible to connect these sensors into the converter
and evaluate the device temperature and if needed, generate warning or fault. ETP block
parameters can be found in:
Parameter ID: 860
SETTINGS
–
> FUNCTIONS -> EXTERNAL THERMAL PROTECTION (ETP)
One free analog input and output are used to connect the temperature sensors.
Mathematical model calculates the optimal
"ETP Current"
, which will be selected as a
signal of the corresponding AOUTx. Voltage drop occurs on AINx, AINx writes it into the
t [s]
Motor
power [W]
F
MIN
Frequency
[Hz]
START command
I. scanning
after start
F
MAX
II.
Fine tuning of
the maximal
power
III.
Technological
conditions change
–
optimization
point shift
█
- optimization output (ID= 423)
–
connected to the frequency setpoint
█
- optimized signal (ID=80)
–
connected to the motor power
(OPT Output)
PAR.ID = 423
Содержание Quatrofrem Series
Страница 2: ...UNIFREM v 3 41x 10 May 2017 Page 2 from 180...
Страница 127: ...UNIFREM v 3 41x 10 May 2017 Page 127 from 180...