Installation Instructions

6224/6224DS Electric Strike

®

Figure 1

DC input is

nonpolarized.

NOTE

!

J1

J2 P2

Switches shown with tripper

depressed, strike lip closed and locked
(switches and tripper on 6224DS only)

Use crimp connectors to
splice field wiring to P2
leads; insulate unused leads

P1

P1 J1A

P1A

SO-12 or SO-24

12 VDC

or

24 VDC

12 VAC            SO-12     12 VDC
     or
24 VAC            SO-24     24 VDC

{
{

J2

Fail safe (FS)

J2

Fail secure (FSE)

S1

S2

1
2
3
4
5
6

S1

S2

1
2
3
4
5
6

Wiring

for DC

supply

Wiring
for AC

supply

4.

Test strike: Apply solenoid power. Fail secure (FSE) lip unlocks.

Fail safe (FS) lip locks. Figure 1 shows status of switches.

5.

Install strike with two #12-24 screws. Make sure clearance

between latch bolt and strike lip is 1/32” (Figure 2). If not,
uninstall strike, adjust (Figure 3), and reinstall.

6.

If latch bolt does not extend far enough to actuate tripper,
install extension (Figure 4). (Tripper on 6224DS only.)

7.

Test door: With strike unlocked, door opens
with latch bolt extended. When door closes,

latch bolt rides over strike lip.

931240_00(4) Copyright © 2004 Ingersoll-Rand. All rights reserved.

Solenoid

89/336/EEC

Standard: 5 A, 30 VDC

Gold: 0.25 A, 30 VDC

SWITCH RATINGS

}

P2

Red (C)
Blue
Yellow
White (C)
Gray
Violet

}

S1

(monitors

tripper)

S2

(monitors

strike lip)

Use crimp

connectors to

splice field wiring

to P1 leads

Tripper

Figure 4

Extension

Figure 3

To adjust strike,
loosen screws 

A, B,

and 

C

 and move

backbox sideways
as necessary

A

B

C

Figure 2

Top view;

faceplate not

shown for clarity

1/32”

Latch bolt

Strike lip

Yellow solenoid wires = 12 VDC, 0.57 A

Black solenoid wires = 24 VDC, 0.29 A

(also shown on strike label)

SOLENOID POWER REQUIREMENTS

Notes:

Deadbolt will not function with this strike.

Check with factory for retrofit applications.

1.

For lock or device preparation, see their directions.

2.

Prepare door for strike (see other side).

3.

Wire strike (Figure 1). (Switches on 6224DS only.)

Double Door Closed Back Mortise or Cylindrical Application

931240-00