18
System components
Personal protection circuit breaker
The personal protection circuit breaker is located in the technical cabinet. The RCD (residual current device) and
two fuses are located in the housing of the personal protection circuit breaker. The tripping threshold of the RCD
is 30 mA. The personal protection circuit breaker has one input and two outputs. The input is connected to the
external socket outlet. The cable colour is white.
The following components are connected to output I:
- Electric heater (Truma)
- On-board charger
- Roof air conditioning system
The cable colour is black. The circuit has a 10 A fuse.
The 230 V sockets are connected to output II.
The cable colour is white. The circuit has a 16 A fuse.
This means the circuits can be identified by the cable colour.
All black and white cables have the same mechanical coding.
If the two output cables were to be interchanged, both circuits would be incorrectly fused.
During all repair work, the 230 V voltage supply must not be connected to the external socket.
All repair work on the 230 V system is only allowed to be carried out by a qualified electrician or
under the supervision of a qualified electrician.
Comply with national regulations.
The valid workshop manual in ElsaPro must be followed.
s599_018
Personal protection
circuit breaker
230 V input
RCD switch/fuse 1 10 A/fuse 2 16 A
Connector view
Technical cabinet
230 V outputs