Description
The Vivo® power supply Bil/Popi/Buri KNX is a KNX de-
vice for rail mounting which produces and monitors the
30 Vdc voltage required to operate the bus system. The
device has an integrated choke which provides the de-
coupling between the power supply and the information
on the bus line. On a KNX bus line can be connected
up to 64 KNX bus devices. The output is protected from
overload and short circuit. The device can support short
interruptions of the mains voltage (max 200 ms).
Functions
• 30 Vdc SELV power supply for a KNX bus line with
max 64 connected devices (Bil KNX)
• Reset of the connected bus line with an internal de-
dicated pushbutton
Main characteristics
• Housing in plastic material
•
Mounting on 35 mm rail (according to EN 60715)
• Protection degree IP20 (installed device)
•
Classification climatic 3K5 and mechanical 3M2 (ac
-
cording to EN 50491-2)
• Pollution degree 2 (according to IEC 60664-1)
• 4 modular units (1 UM = 18 mm)
• Dimensions 72 x 90 x 62 mm (WxHxD)
•
Weight 225 g
Environmental conditions
•
Operating temperature: - 5 ... + 45°C
•
Storage temperature: - 25 ... + 55°C
•
Transport temperature: - 25 ... + 70°C
•
Relative humidity: 95% not condensing
Warning! Incorrect disposal of this product
may cause serious damage to the envi-
ronment and human health. Please be infor-
med about the correct disposal procedures
for waste collecting and processing provi-
ded by local authorities.
Technical data
Power supply
•
Voltage 230/110 Vac, 50/60 Hz
• Power consumption 22 W (power losses < 3 W)
Outputs
•
Bus line voltage: 30 Vdc +1/-2 Vdc SELV
• Rated current (total outputs): 640-320-160 mA
• Buffer time: 200 ms
• Bus line connection: KNX ternminal block (black/red)
included in delivery
Switching, display and connection elements
The device is equipped with a reset pushbutton, ter-
minal blocks for mains voltage 230/110 Vac, KNX bus
line.
Planning
Planning a KNX bus installation, the use of a 640 mA
power supply unit requires to take into account the fol-
lowing guidelines:
• the maximum number of bus devices connected is
64;
•
the maximum length of a line segment is 350 m, me
-
1) Terminal blocks for power supply 110-230 Vac 50/60 Hz
2) Status LED
3) Reset pushbutton (internal)
4) Terminal block for KNX bus line
asured along the line between the power supply and
the furthest bus device;
• the maximum distance between two bus devices
cannot exceed 700 m;
• the maximum length of a bus line is 1000 m, keeping
into account all segments.
At the same bus line can be connected not more than
two power supplies. A second power supply may be
necessary when the installation in distribution boards
requires a particular concentration of the bus devices
(tipically more than 30 units installed within 10 m). In
this case a power supply has to be installed near the
group of devices. Between two power supplies installed
on the same bus line a minimum distance of 200 m is
required, measured along the line.
Mounting
The device has degree of protection IP20, and is the-
refore suitable for use in dry interior rooms. The hou-
sing is made for rail mounting according to EN 60715
in boards or cabinets for electrical distribution. The in-
stallation is in horizontal position, the correct position
is when the terminals for KNX bus line and auxiliary
Warning! In order to supply the KNX bus li-
nes use only a KNX bus power supply (e.g.
Vivo Cursa KNX). The use of other power
supplies can compromise the communica-
tion and damage the devices connected to
the bus.
output are located at the bottom and the terminals
( , L, N) for connecting the mains power supply
230/110 Vac are located at the top. For the installation
of the device on the rail proceed as follows:
• with the aid of a tool bring the locking device in the
fully lowered position (a);
•
place the upper edge of the rear inner profile on the
upper edge of the rail (b);
• rotate the device towards the rail (c);
• push the locking device upward until it stops (d).
Before removing the device, be sure terminals for bus
and have been extracted from his slots. Use a screwdri-
ver to slide down the locking device and remove the
device from the rail.
a
b
d
Note.
When mounting the device in boards
and cabinets it shall be provided the necessary
ventilation so that the temperature can be kept
within the operating range of the device.
Electrical connections
Main supply 230/110 Vac
The connection to the 230/110 main supply Vac is
made with screw terminals ( , L, N) located on the
front. Characteristics of the KNX terminal block:
• spring clamping of conductors
• 4 seats for conductors for each polarity
• terminal suitable for KNX bus cable with single-wire
conductors and diameter between 0.6 and 0.8 mm
•
recommended wire stripping approx. 5 mm
•
color codification: red = + (positive) bus conductor,
black = - (negative) bus conductor
Configuration and commissioning
Configuration
The device does not require any configuration with
ETS
®
(Engineering Tool Software) tool. The application
software are available in order to add to an ETS project
an Bil/Popi/Buri KNX power supply.
Commissioning
For the commissioning of the device turn on the mains
power supply 230/110 Vac to which the device is con-
nected. The green LED marked “ON” indicates the de-
vice operating.
Reset
The device has a reset pushbutton. After a reset, the
bus line is not powered for 20 seconds and the bus de-
vices connected are restored to their original condition.
During this interval of time the reset LED (red) is turned
permanently on.
Marks
• KNX
• CE: the device complies with the Low Voltage Direc-
tive (2006/95/EC) and the Electromagnetic Compa
-
tibility Directive (2004/108/EC). Tests carried out ac-
cording to EN 50491-2:2010, EN 50491-3:2009, EN
50491-4-1:2012, EN 50491-5-1:2010, EN 50491-5-
2:2010, EN 50428:2005 + A1:2007 + A2:2009
Maintenance
The device is maintenance-free. To clean use a dry
cloth. It must be avoided the use of solvents or other
aggressive substances.
Disposal
At the end of its useful life the product
described in this datasheet is classified
as waste from electronic equipment in
accordance with the European Directive
2002/96/EC (RAEE), and cannot be dispo-
sed together with the municipal undifferen-
tiated solid waste.
Warnings
•
Installation, electrical connection, configuration and
commissioning of the device can only be carried out
by qualified personnel in compliance with the appli
-
cable technical standards and laws of the respective
countries
• The power supply line to which the device is con-
nected must be equipped with an easily accessible
disconnecting device with minimum separation di-
stance between contacts of 3 mm
• Opening the housing of the device causes the imme-
diate end of the warranty period
• In case of tampering, the compliance with the es-
sential requirements of the applicable directives,
for which the device has been certified, is no longer
guaranteed
• Vivo® KNX defective devices must be returned to
the manufacturer at the following address: Vivo
Suisse Sagl,
Viale dei Faggi 20
, CH 6900 Lugano
Other information
• The instruction sheet must be delivered to the end cu-
stomer with the project documentation
• For further information on the product, please con-
tact the Vivo® technical support at the e-mail ad-
dress: [email protected] or visit the
website www.vivoknx.com
• Each Vivo® device has a unique serial number on
the label. The serial number can be used by instal-
lers or system integrators for documentation purpo-
ses and has to be added in each communication
addressed to the Vivo technical support in case of
malfunctioning of the device
• Vivo® is a registered trademark of Vivo Suisse Sagl
• KNX
®
and ETS
®
are registered trademarks of KNX
Association cvba, Brussels
© Vivo Suisse Sagl 2017. The company reserves the right to make
changes to this documentation without notice.
upper front of the device. Characteristics of the terminal
blocks:
• screw clamping of conductors
•
maximum cross section of conductor 2.5 mm²
• recommended wire stripping approx. 6 mm
•
torque max 0.5 Nm
KNX bus line
The connection to the KNX bus line is made with the
terminal block (black/red) included in delivery and in-
serted into the slot located on the left bottom part of the
i
Warning! The electrical connection of the
device can be carried out only by qualified
personnel. The incorrect installation may
result in electric shock or fire. Before ma
-
king the electrical connections, make sure
the power supply has been turned off.
!
!
c
!
Power supply KNX 160/320/640mA
Code:K.BUR.01A.20N.WO
K.POP.01A.20N.WO - K.BIL.01A.20N.WO
Instructions
EN
TP1
S
Its a registred brand of
Vivo Suisse Sagl
HQ
Viale dei Faggi 20
CH-6900 Lugano
Tel. +41919800044
www.vivoknx.com
Code
Description
K.BUR.01A.20N.WO
Buri KNX - 160 mA
K.POP.01A.20N.WO
Popi KNX - 320 mA
K.BIL.01A.20N.WO
Bil KNX - 640 mA