INSTALLATION, OPERATION, CONFIGURATION AND MAINTENANCE MANUAL
February/2020
VHC10-P
HART
®
4 – 20 mA CONVERTER
panel model
Страница 1: ...INSTALLATION OPERATION CONFIGURATION AND MAINTENANCE MANUAL February 2020 VHC10 P HART 4 20 mA CONVERTER panel model...
Страница 2: ...ompliance with the hardware and software versions described herein However due to the dynamic development and version upgrades the possibility of technical deviations cannot be ruled out We cannot acc...
Страница 3: ...3 CONFIGURATION 8 3 1 JUMPERS FOR LOCAL ADJUST AND WRITE PROTECTION 8 3 2 HART PROGRAMMER 8 3 3 CONFIGURATION PARAMETERS 9 3 4 PROGRAMMING TREE FOR HART CONFIGURATOR 10 3 5 SAFE OUTPUT 12 3 6 FDT DTM...
Страница 4: ...process and equipment Install equipment only in operation compatible areas with the proper connections and protections Use proper safety equipment for any handling device in field Turn area power off...
Страница 5: ...t at the beginning of its operating cycle with the converter in slave mode being completed by the user by changing the use mode to master Configurations can be performed using a HART configurator or t...
Страница 6: ...nverter s current channels Converter connections are shown in figure 2 1 2 channel model Note at the top that the converter is powered by a voltage source 12 to 45 Vdc OUT1 and its input is polarized...
Страница 7: ...rter output currents will indicate the variables read from the transmitter as indicated in the figures Communication terminals 5 and 6 of the converter must be connected over the 250 ohm load where th...
Страница 8: ...SABLED Figure 3 1 Hardware write protection 3 2 HART PROGRAMMER The configuration of the equipment can be performed using a programmer compatible with HART technology Vivace offers VCI10 HART line int...
Страница 9: ...ds the master mode will be enabled automatically b Localize the conversor Using a HART configurator poll device at address one 1 or at the address modified by user user c Change mode to Configuration...
Страница 10: ...s will start automatically generating the 4 20 mA output currents proportional to the values configured in the parameters of the respective working ranges and current calibrations HART standard CONFIG...
Страница 11: ...HART Master Mode Write Protection and Communication Preambles TRIM User can adjust the output currents of the converter Figure 3 4 shows the assembly diagram for the TRIM of the current OUT1 of the VH...
Страница 12: ...the respective monitored variable as soon as the connection with the slave equipment is re established or when the configuration mode is ended 3 6 FDT DTM CONFIGURATION Tools based on FDT DTM Ex PACT...
Страница 13: ...g case 4 2 IDENTIFICATION VHC10 P has an identification tag attached to its front face specifying model manufacturer and connections as shown in Figure 4 2 It also has a side label with the converter...
Страница 14: ...rature and mechanical connection Table 4 1 Specifications for VHC10 P converter 4 5 SPARE PARTS 4 Way VHC10 P Protection Connector upon request Accuracy 0 03 of calibrated span Comunication Protocol H...
Страница 15: ...g spare parts but it is strongly recommended to forward it to Vivace for diagnosis and maintenance in cases of doubt or impossibility of correction by the user For details about the product warranty s...
Страница 16: ...o Buying Invoice n COMMERCIAL CONTACT Complete Name Position Phone and Extension Fax e mail TECHNICAL CONTACT Complete Name Position Phone and Extension Fax e mail EQUIPMENT DATA Model Serial Num PROC...
Страница 17: ...RT 4 20 mA CONVERTER INSTALLATION OPERATION CONFIGURATION AND MAINTENANCE MANUAL _______________________________________________________________________________________________________________________...