background image

INSTALLATION INSTRUCTIONS

Inground & Well Lights

Architectural Series

1181/1182

IMPORTANT NOTE:

•  Luminaire must be installed and grounded in accordance with the National Electrical Code (NEC) and local codes.
•  All conduit entries must be sealed from moisture. Use appropriate sealing material on conduit fittings and conduit closure plugs.
•  Luminaire is wet location listed and suitable for mounting in-grade. 
•  Suitable for all types of construction including poured concrete construction and in-soil construction.

WARNING:  Debris must be kept clear from top and interior of in-grade fixtures. Exessive heat could occur that may create a fire hazard and/
or harm the fixture components.  Specific attention must be made to never install in-grade fixtures in mulch, wood chips, or other potentially 
ignitable materials.  Faliure to do so will void warranty and may result in serious injury and/or damage the fixture and/or property.
MAINTENANCE: To assure proper orrientation and efficiency and to prevent luminaire overheating, lens must be kept clear of debris, dirt, 
leaves,trash and mineral deposits from water. A regular schedule maintenance program is recommended.
NOTE: Save these instructions for future reference.

1625 Surveyor Avenue • Simi Valley, CA 93063 • (805) 527-0987 • (800) 766-VISTA (8478)

FAX: (888) 670-VISTA (8478) • [email protected] • www.vistapro.com

Vista Professional Outdoor Lighting reserves the right to modify the design and/or construction of the fixture shown without further notification.

IN-GRADE SOIL INSTALLATION:
IMPORTANT NOTE: 

Temporary cover plate and vinyl label must remain in place 

during housing installation.

PRECAUTION:

  Adequate drainage must be provided during installation.  It is 

recommended the luminaire be surrounded by 3” to 4” of pea gravel along the 
sides and minimum of 6” of pea gravel at the bottom and beneath the luminaire 
housing.  Top of the luminaire must be above grade so rain and irrigation water will 
not accumulate for long periods of time.
1. 

To prevent electrical shock, turn main power off at circuit breaker.

2. 

Dig a hole approximately 12” in diameter to a depth suitable to make top of 
temporary cover plate 3/4” above grade (see figure 1).  Pea gravel is required 
for seating the luminaire housing and providing necessary drainage.

3. 

Connect conduit to housing. UL listed flexible conduit is recommended for in 
and out connections to ease fixture positioning.                          

IMPORTANT NOTE: If conduit, of the rigid metallic type, is connected 
to the enclosure housing, the hub (by others) shall be connected to the 
conduit before the hub is connected to the enclosure housing.

4. 

Plug and unused NPT holes with closure plugs (provided).

5. 

Position fixture within the hole and back fill with pea gravel.  Only the 
uppermost layer, 3” maximum, should be soil or organic mulch.

6. 

To pull supply conductor wiring, first remove and retain the Temporary Cover 
Plate and Plate Screws by piercing through the label at the screws locations to 
access the screws.

7. 

Pull electrical supply wires (line in) through conduit opening.  Stuff the wire 
loop back through the conduit opening (line out).

8. 

Reinstall the Temporary Cover Plate and Vinyl Label using the cover screws.

CONCRETE POUR INSTALLATION:
IMPORTANT NOTE: 

Temporary cover plate and vinyl label must remain in place 

during housing installation.

PRECAUTION:

  Adequate drainage must be provided during installation.  It is 

recommended the luminaire be surrounded by 3” to 4” of pea gravel along the sides 
and minimum of 6” of pea gravel at the bottom and beneath the luminaire housing.  
Top of the luminaire must be FLUSH with finished grade.
1. 

To prevent electrical shock, turn main power off at circuit breaker.

2. 

Dig a hole approximately 12” in diameter to a depth suitable to make top of 
temporary cover plate FLUSH with finished grade (see figure 2). Pea gravel is 
required for seating the luminaire housing and providing necessary drainage.

3. 

Connect conduit to housing.  UL listed flexible conduit is recommended for in 
and out connections to ease fixture positioning. 

IMPORTANT NOTE: If conduit, of the rigid metallic type, is connected 
to the enclosure housing, the hub (by others) shall be connected to the 
conduit before the hub is connected to the enclosure housing.

4. 

Plug and unused NPT holes with closure plugs (provided).

5. 

Position fixture within the hole and back fill with pea gravel.  The uppermost 
layer, 6” minimum, should be left for poured concrete.

6. 

To keep housing from floating during the concrete pour, the Rebar Mount 
Bracket (RMB) accessory should be used to affix the housing to wire/rebar grid 
using standard masonry methods.

7. 

To pull supply conductor wiring, first remove and retain the Temporary Cover 
Plate and Plate Screws by piercing through the label at the screw locations to 
access the screws.

8. 

Pull electrical supply wires (line in) through conduit opening.  Stuff the wire 
loop back through the conduit opening (line out).

9. 

Reinstall the Temporary Cover Plate and Vinyl Label using the cover screws.

10.  Pour the concrete at least 3” thick.  Trowel concrete so it is even with the vinyl 

label.  Allow concrete to cure.

CONDUIT

REBAR

TEMPORARY COVER

PLATE & VINYL LABEL

REBAR MOUNT BRACKET

(RBK ACCESSORY)

FIXTURE HOUSING

CONCRETE

EARTH

PEA GRAVEL

CONDUIT

EARTH

PEA GRAVEL

TEMPORARY COVER

PLATE & VINYL LABEL

FIXTURE HOUSING

Отзывы: